Troubleshooting
•
Do a check of the encoder connection.
•
PMS motor has exceeded the pull-out torque.
12.10.131 Fault 62 - Run disable
Cause
Run enable signal is low.
Troubleshooting
Do a check of the reason for the Run enable signal.
12.10.132 Fault 63 - Quick stop
Cause
Command for quick stop received from digital input or fieldbus.
This fault is type A fault (Alarm).
Troubleshooting
Reset the fault.
12.10.133 Fault 64 - Input switch open
Cause
Drive input switch is open.
This fault is type A fault (Alarm)
Troubleshooting
Do a check of the main power switch of the drive.
12.10.134 Fault 65 - Measured Temperature
Cause
Shows temperature measurement fault for option board OPTBH or OPTB8.
•
Temperature exceeded set limit.
•
Sensor disconnected.
•
Short circuit.
Specifications
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908| 159
Danfoss A/S © 2019.07
Содержание VACON NX FI4
Страница 1: ...Operating Guide VACON NX Inverters FI4 FI8...
Страница 2: ......
Страница 164: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 164 Danfoss A S 2019 07...
Страница 165: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 165 Danfoss A S 2019 07...