12.3.4 Cable Sizes for 640–1100 V DC (525–690 V AC)
Table 28: Cable Sizes for 640–1100 V DC (525–690 V AC)
Enclosure
size
Drive type
I
L
[A]
Supply cable
Cu [mm
2
]
Motor cable Cu
[mm
2
]
Main terminal cable
[mm
2
]
Earth terminal ca-
ble [mm
2
]
FI6
NXI_0004 6–0007 6
3–7
2*2.5
3*2.5+2.5
2.5–50 Cu
2.5–35
6–50 Al
NXI_0010 6–0013 6
10–13
2*2.5
3*2.5+2.5
2.5–50 Cu
2.5–35
6–50 Al
NXI_0018 6
18
2*4
3*4+4
2.5–50 Cu
2.5–35
6–50 Al
NXI_0022 6
22
2*6
3*6+6
2.5–50 Cu
2.5–35
6–50 Al
NXI_0027 6–0034 6
27–34
2*10
3*10+10
2.5–50 Cu
2.5–35
6–50 Al
FI7
NXI_0041 6
41
2*100
3*10+10
2.5–50 Cu
6–50
6–50 Al
NXI_0052 6
52
2*16
3*16+16
2.5–50 Cu
6–50
6–50 Al
FI8
NXI_0062–0080 6
62–80
2*25
3*25+16
25–95 Cu/Al
25–95
NXI_0100 6
100
2*35
3*35+16
12.4 Cable Stripping Lengths
for parts of cables to be stripped and check the corresponding stripping length in the table.
Specifications
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
116 | Danfoss A/S © 2019.07