Too low a supply voltage
•
AC drive internal fault
•
A defective input fuse
•
The external charge switch is not closed.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
•
If there is a temporary supply voltage break, reset the fault and start the drive again.
•
Do a check of the supply voltage. If the supply voltage is sufficient, there is an internal fault.
•
Ask instructions from the local distributor.
12.10.45 Fault 10 - Input line supervision, Subcode S1 - Phase supervision diode supply
Cause
The input line phase is missing.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
Do a check of the supply voltage, the fuses, and supply cable.
12.10.46 Fault 11 - Output phase supervision, Subcode S1 - Common output phase supervision
Cause
The measurement of current tells that there is no current in 1 motor phase.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
Do a check of the motor cable and the motor.
12.10.47 Fault 11 - Output phase supervision, Subcode S2 - Additional closed loop control output
phase fault
Cause
The measurement of current tells that there is no current in 1 motor phase.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
Do a check of the motor cable and the motor.
Specifications
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908| 137