103 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
• • • CAUTION • • •
Do not connect Mega Ohmmeter while the compressor is under a vacuum; this may cause damage.
1. Place the leads on terminal 1 & 3 of the pressure/temperature sensor.
2. The temperature sensor is a 10KΩ @ 77°F (25°C) negative temperature coefficient (NTC)
thermistor.
3.7.1.13.2 Temperature/
Pressure Sensor
Verification
Figure 125 - Temperature/
Pressure Sensor Pin Location
3. Compare the compressor pressure readout to the gauge pressure value.
4. The values should not be greater than the following:
• Suction Sensor - 1.7psi (12kPa)
• Discharge Sensor - 7.25psi (50kPa)
Running Check
1. Connect to the compressor with the SMT.
2. Compare pressure and temperature readout from compressor to readings from a calibrated
gauge set and thermometer placed as close to the sensor location as possible.
Table 28 - Temperature/
Pressure Sensor Torque
Specifications
Description
Nm
Ft.Lb.
In.Lb.
Suction Temperature Sensor
10
7
89
Discharge Temperature Sensor
10
7
89
Pin 1
Pin 2
Pin 3
Pin 4
Notch
Содержание Turbocor VTT Series
Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...