Compressor Components
• • • CAUTION • • •
The ICM valve must not be in its fully opened position while the ICAD motor is calibrated with the
valve. Therefore, if the opening degree of the ICM valve was changed from the factory setting, it
should be set to an opening degree between 0% and 75% using the manual magnet tool. To easily
ensure correct positioning, turn the manual tool counter-clockwise until it is clear that it cannot be
turned further.
IFV Actuator Installation
1. Generously lubricate the O-ring groove on the adapter/valve stem and on the new O-ring with
the Molykote G 4500 grease provided.
2. Install the IFV Actuator to the Bonnet/Function Module ensure the actuator is fully inserted with
the wire connection ports facing up.
3. Secure the IFV Actuator to the Bonnet/Function Module using the three (3) set screws and a 2.5
mm hex bit. Torque to specification.
4. Attach the Red (power) and Black (signal) cables to the IFV by turning the collars, located on the
cable ends, in a clockwise rotation.
5. Restore power to the Compressor.
Figure 20 - IFV Actuator
Install
3.2.2.2 Programming
(Required)
Programming is required anytime the IFV Controller is replaced.
1. Hold the
Edit/Enter
button for 2 seconds to enter the programming mode.
2. Press the
Up Arrow
button until you reach Parameter 04.
3. Press the
Enter/Edit
button.
4. Press the
Up Arrow
button to select 10.
5. Press the
Enter/Edit
button.
6. Press the
Up Arrow
button and go to Parameter 10.
7. Press the
Edit/Enter
button.
8. Press the
Up Arrow
button until you reach 11 (Password).
9. Press the
Enter/Edit
button.
Содержание Turbocor VTT Series
Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...