![Danfoss Turbocor VTT Series Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/danfoss/turbocor-vtt-series/turbocor-vtt-series_service-manual_506651046.webp)
46 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
11. Once the valve has cooled back down, reinstall the electronic power head and retaining clip if
removed.
Figure 38 - Brazing the EXV
3.2.7.4 Torque
Specifications
Description
Nm
Ft.Lb.
In.Lb.
Flange, SHCS, M14x40 (Revision A)
70
52
620
Flange, SHCS, M8x25 (Revisions B and later)
30
22
266
Table 11 - EXV Torque
Specifications
3.2.8 EXV Cable
The EXV Cable connects the CCM to the EXV.
Figure 39 - EXV Cable