Compressor Components
Temperature
º C
Resistance
Ω
Temperature
º C
Resistance
Ω
Temperature
º C
Resistance
Ω
-50
803.1
40
1155.4
130
1498.3
-40
842.7
50
1194.0
140
1535.8
-30
882.2
60
1232.4
150
1573.3
-20
921.6
70
1270.8
160
1610.5
-10
960.9
80
1309.0
170
1647.7
0
1000.0
90
1347.1
180
1684.8
10
1039.0
100
1385.1
190
1721.7
20
1077.9
110
1422.9
200
1758.6
30
1116.7
120
1460.7
Table 20 - Stator
Thermistor R/T Curve
9. Verify resistance of each circuit at the external connector to housing (ground).
• Should be “open.”
10. If the Stator Temperature Sensor Feed Through is suspected to have a problem, remove it and
test as above directly at the internal connector. Refer to the
“Stator Temperature Sensor Feed
section of this manual.
11. Restore power to the Compressor.
NOTE
Measured values must be within
±
10% of the values in Table 20 (Stator Thermistor R/T Curve).
Содержание Turbocor VTT Series
Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...