Troubleshooting
Fault Reset:
A fault that does not require a
power cycle to clear (non-critical) can be reset in
the following manner: Interlock must be closed,
set the Demand to 0 and afterwards to a value
greater than 0. Now the fault is reset and the
compressor is ready to run. The assumption is
that the cause of the fault has been rectified.
A fault demanding a power cycle (Lock-Out
Fault) is resettable by cycling the mains power
to the compressor. The assumption is that the
cause of the fault has been rectified. See Table 22
(Compressor Faults).