M-SV-001-EN Rev.E
Troubleshooting
Figure 98 - Bearing
Calibration Flow
Could the shaft run
and levitate without
issue
prior to
calibration?
Does shaft
levitate after
Save to
EEPROM?
Does shaft levitate
after Save to
EEPROM?
You may need to
recalibrate upwards of 3
times. Each time saving
to EEPROM, creating a
calibration report, and
cycling power
Save to EEPROM,
Validate shaft, create
a calibration report,
and cycle power
Do not save
calibration to
EEPROM. Create a
calibration report.
Return compressor to
normal operation
No
Yes
No
Successful Re-
Calibration.
Return
compressor to
normal operation
Shaft is
obstructed
or bearing system
issue
Verify the
bearings
Verify the
bearing
sensors
Yes
Verify the PWM
If
verification passes, but
the bearings cannot be
validated, repeat the
calibration process
If the bearings still
cannot be calibrated,
the shaft is obstructed
and the compressor
must be replaced
Yes
No
Start Bearing
Calibration
End
End
Содержание Turbocor TG230
Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 4: ...4 of 132 M SV 001 EN Rev E THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 12: ...12 of 132 M SV 001 EN Rev E THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 28: ...28 of 132 M SV 001 EN Rev E Compressor Fundamentals Figure 18 Compressor Energy and Control Flow Block Diagram ...
Страница 61: ...61 of 132 M SV 001 EN Rev E Compressor Components Figure 56 Stator Thermistor R T Curve 1 ...
Страница 120: ...120 of 132 M SV 001 EN Rev E THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 130: ...130 of 132 M SV 001 EN Rev E Notes ...