6.1  Net configuration with 

modbus-RTU protocol

6.0  Modbus connection

For 

RS-485

 connections with 

Modbus-RTU

 protocol follow the scheme below.

AK-RC 113

7     8

7.1  Diagnostics by means of 

alarm codes

7.0 Diagnostics

In the event of any anomalies of the

 AK-RC 113

, it notifies the operator by means of the alarm codes 

displayed on the display and an audible signal emitted by a buzzer inside the control panel. The EL 

and EH temperature alarms remain visible even after their return (alarm icon lights on) until their 

acknowledgment (by pressing the key). If an alarm condition occurs, one of the following messages 

will be displayed on the display:

Alarm code

Possible cause

Solution

E0

Cold room temperature sensor not working properly

•  Check that cold room temperature 

sensor is working properly

•  If the problem persists, replace the 

sensor

E1

Defrost sensor not working properly

(In this case defrosts will last time d3)

•  Check that defrost sensor is 

working properly

•  If the problems persists, replace the 

sensor

E2

Eeprom alarm

An EEPROM memory alarm has been detected

(All outputs except the alarm one are deactivated)

•  Switch unit off and back on 

E8

Man in cold room alarm

•  Reset the alarm input inside the 

cold room

Ec

Compressor protection tripped

(e.g. thermal protection or max pressure switch)

(All outputs except the alarm one – where applicable – 

are deactivated)

•  Check that compressor is working 

properly

•  Check compressor absorption
•  If the problem persists, contact the 

technical assistance service

Ed

Open door Alarm

.

When the door is opened and after tdo time, it’s setted 

back the normal functioning giving door open alarm 

(Ed).

•  Check door switch status 
•  Check door switch connections
•  If the problem persists contact the 

technical assistance service

E9

Cell light alarm.

The light of the cell has been on for a time greater than 

tdo.

•  Turn off the light

EH

Maximum temperature alarm.

The temperature inside the cold room has exceeded 

the max. temperature alarm setting (see variables A2, 

user programming level

)

•  Check that the compressor is 

working properly.

•  Sensor not reading temperature 

properly or compressor start/stop 
control not working.

EL

Minimum temperature alarm.

The temperature inside the cold room has exceeded 

the min. temperature alarm setting (see variables A1, 

user programming level

).

•  Check that the compressor is 

working properly.

•  Sensor not reading temperature 

properly or compressor start/stop 
control not working.

Содержание OPTYMA

Страница 1: ...User Guide Optyma control AK RC 113 three phase...

Страница 2: ...1 Control panel 9 5 2 Front keypad 9 5 3 LED display 9 5 4 General 10 5 5 Key to symbols 10 5 6 Setting and displaying the set points 10 5 7 Level 1 programming user level 10 5 8 List of Level 1 varia...

Страница 3: ...0 V AC 10 50 60Hz 400 V AC 10 50 60Hz Load type 3 phase 3 phase Operating temperature 5 40 C 5 40 C Storage temperature 25 55 C 25 55 C Relative ambient humidity from 30 to 95 RH w out condensate from...

Страница 4: ...lectrical panel Signaling with LED icons of the plant status Applications Complete management of 3 phase static or ventilated refrigeration systems with off cycle or electrical defrosting and with dir...

Страница 5: ...easy use and internal access The operator should not come to be in a dangerous situation when he is working on the panel The height must however be between 0 6 and 1 7 meters from the floor Install t...

Страница 6: ...cables as much as possible preventing the wiring from taking the spiral shape that is harmful to possible inductive effects on the electronics If it s necessary to extend the probes conductors must be...

Страница 7: ...to the compressor motor as indicated in the following chapter After turning on the electrical panel check the correct current absorption of the various loads After operating the system for a few hours...

Страница 8: ...meter verify the effective absorption Fig 18 Close the front panel making sure that all cables are inside the box and that the box gasket is correctly housed Fig 20 Power up the panel and carry out th...

Страница 9: ...n Manual defrost 5 Room light 6 5 3 LED display Cold room temperature parameter settings 7 Stand by icon LED OFF Electrical panel OFF LED ON Electrical panel ON and in regulation LED flashing Electric...

Страница 10: ...lity the following symbols are used the UP key is used to increase values and mute the alarm the DOWN key is used to decrease values and force defrosting 5 4 General 5 5 Key to symbols 5 6 Setting and...

Страница 11: ...recirculation Fans working time for F6 0 240 sec 10 sec dE Evaporator probe presence If the evaporator sensor is disabled defrosts are carried out cyclically with period d0 defrosting ends when an ext...

Страница 12: ...ng on of the compressor 0 15 min 0 min CAL Cold room sensor value correction 10 10 C 0 C CE1 Compressor ON operating time in the event of a faulty ambient probe emergency operation With CE1 0 the emer...

Страница 13: ...rature setting for auxiliary relay 45 45 C 0 C nSC Correction factor for the SET button during night operation energy saving with In1 or In2 8 or 8 During night operation the control set is Set Contro...

Страница 14: ...s defrost 5 16 Pump down function 5 17 Password function Set the parameter d1 2 for the management of the resistance defrost with time limit During defrosting the defrost relay is activated if the tem...

Страница 15: ...ted All outputs except the alarm one are deactivated Switch unit off and back on E8 Man in cold room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal prote...

Страница 16: ...rt the circuit breaker checking all the absorptions to identify any anomalies Intervention of the secondary circuit protection fuse on the transformer Restore the fuse Glass fuse 10x20 F250mA 250V Che...

Страница 17: ...wer supply Prevent unauthorized personnel from being present in the intervention area Put signals to indicate that the machine is under maintenance Wear work clothes suits gloves shoes headgear suitab...

Страница 18: ...15 JB01 2 JB01 3 JB01 13 JB01 14 JB01 15 JB01 5 5 JB01 6 6 JB01 7 7 JB01 8 8 JB01 4 4 JB01 9 9 JB01 10 L10 JB01 11 L11 OPTYMA Control three phase 4 HP OPTYMA Control three phase 7 5 HP MODBUS B Power...

Страница 19: ...bonate screw cover 9 Auxiliary circuits transformer N B with inside a glass fuse 10 x 20 F250 mA 250 V 10 Connector for linking panel and the electronic card 11 Front panel 12 Electronic card 13 Elect...

Страница 20: ...t notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed All trademarks in this material are propert...

Отзывы: