BC317523579312en-000101 | 11

5.8  List of Level 1 variables

 

(user level)

To access the second programming level press the UP (

) and DOWN (

) keys and the LIGHT key 

simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1.  Select the variable to be modified by pressing the UP (

) and DOWN (

) keys.

  When the parameter has been selected it is possible to:
2.  View the setting by pressing the SET key.
3.  Modify the setting by holding the SET key down and pressing the (

) or (

) key.

4.  When configuration settings have been completed you can exit the menu by pressing the (

) and 

(

) keys simultaneously and keeping them pressed until the room temperature reappears.

5.  Changes are saved automatically when you exit the configuration menu.
6.  Press the STAND-BY key to enable electronic control.

5.9  Level 2 programming

 

(installer level)

5.10  List of Level 2 variables

 

(installer level)

Variables Meaning

Value

Default

F3

Fan status with compressor off

0 = Fans run continuously 

1 = Fans only run when

compressor is working 

2 = Fans disabled

1

F4

Fan pause during defrosting

0 = Fans run during defrost

1 = Fans do not run during 

defrost

1

F6

Evaporator fans activation for air recirculation.

The fans are activated for a time defined by F7 if they 

have not started operating for the time F6. If the time 

of activation coincides with the defrost phase,

the defrost end is still awaited.

0 – 240 min

0 = (function not activated)

0 min

F7

Duration of activation of the evaporator fans for air 

recirculation

Fans working time for F6

0 – 240 sec

10 sec

dE  

Evaporator probe presence

If the evaporator sensor is disabled, defrosts are 

carried out cyclically with period d0: defrosting ends 

when an external device trips and closes the remote 

defrost contact or when time d3 expires.

0 = evaporator sensor present

1 = no evaporator sensor 

0

Variables Meaning

Value

Default

r0

Temperature difference

 compared to main SETPOINT

0.2 – 10 °C

2 °C

d0

Defrost interval

 (hours)

If 

d0

 = 0 cyclical defrosts Off

0 – 24 hours

4 hours

d2

End-of-defrost setpoint

Defrost is not executed if the temperature read by the defrost 
sensor is greater than 

d2

.

(If the sensor is faulty defrost is stopped on time set by the d3 
parameter)

-35 – 45 °C

15 °C

d3

Max defrost duration

 (minutes)

1 – 240 min

25 min

d7

Drip duration

 (minutes)

At the end of defrost the compressor and fans remain at standstill 
for time 

d7

, the defrost LED on the front panel flashes.

0 – 10 min

0 min

F5

Fan pause 

after defrost (minutes)

Allows fans to be kept at standstill for a time 

F5

 after dripping. This 

time begins at the end of dripping. If no dripping has been set the 
fan pause starts directly at the end of defrost.

0 – 10 min

0 min

A1

Minimum temperature alarm

Allows user to define a minimum temperature for the room being 
refrigerated. Below value 

A1

 an alarm trips: the alarm LED flashes, 

displayed temperature flashes and the buzzer sounds to indicate 
the problem.

-45 – (A2-1) °C

-45 °C

A2

Maximum temperature alarm

Allows user to define a maximum temperature for the room being 
refrigerated. Above value 

A2

 an alarm trips: the alarm LED flashes, 

displayed temperature flashes and the buzzer sounds to indicate 
the problem.

(A1+1) – 99 °C

99 °C

tEu

Evaporator sensor temperature display

 

(displays nothing if 

dE =1

)

evaporator 

temperature

read only

Содержание OPTYMA

Страница 1: ...User Guide Optyma control AK RC 113 three phase...

Страница 2: ...1 Control panel 9 5 2 Front keypad 9 5 3 LED display 9 5 4 General 10 5 5 Key to symbols 10 5 6 Setting and displaying the set points 10 5 7 Level 1 programming user level 10 5 8 List of Level 1 varia...

Страница 3: ...0 V AC 10 50 60Hz 400 V AC 10 50 60Hz Load type 3 phase 3 phase Operating temperature 5 40 C 5 40 C Storage temperature 25 55 C 25 55 C Relative ambient humidity from 30 to 95 RH w out condensate from...

Страница 4: ...lectrical panel Signaling with LED icons of the plant status Applications Complete management of 3 phase static or ventilated refrigeration systems with off cycle or electrical defrosting and with dir...

Страница 5: ...easy use and internal access The operator should not come to be in a dangerous situation when he is working on the panel The height must however be between 0 6 and 1 7 meters from the floor Install t...

Страница 6: ...cables as much as possible preventing the wiring from taking the spiral shape that is harmful to possible inductive effects on the electronics If it s necessary to extend the probes conductors must be...

Страница 7: ...to the compressor motor as indicated in the following chapter After turning on the electrical panel check the correct current absorption of the various loads After operating the system for a few hours...

Страница 8: ...meter verify the effective absorption Fig 18 Close the front panel making sure that all cables are inside the box and that the box gasket is correctly housed Fig 20 Power up the panel and carry out th...

Страница 9: ...n Manual defrost 5 Room light 6 5 3 LED display Cold room temperature parameter settings 7 Stand by icon LED OFF Electrical panel OFF LED ON Electrical panel ON and in regulation LED flashing Electric...

Страница 10: ...lity the following symbols are used the UP key is used to increase values and mute the alarm the DOWN key is used to decrease values and force defrosting 5 4 General 5 5 Key to symbols 5 6 Setting and...

Страница 11: ...recirculation Fans working time for F6 0 240 sec 10 sec dE Evaporator probe presence If the evaporator sensor is disabled defrosts are carried out cyclically with period d0 defrosting ends when an ext...

Страница 12: ...ng on of the compressor 0 15 min 0 min CAL Cold room sensor value correction 10 10 C 0 C CE1 Compressor ON operating time in the event of a faulty ambient probe emergency operation With CE1 0 the emer...

Страница 13: ...rature setting for auxiliary relay 45 45 C 0 C nSC Correction factor for the SET button during night operation energy saving with In1 or In2 8 or 8 During night operation the control set is Set Contro...

Страница 14: ...s defrost 5 16 Pump down function 5 17 Password function Set the parameter d1 2 for the management of the resistance defrost with time limit During defrosting the defrost relay is activated if the tem...

Страница 15: ...ted All outputs except the alarm one are deactivated Switch unit off and back on E8 Man in cold room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal prote...

Страница 16: ...rt the circuit breaker checking all the absorptions to identify any anomalies Intervention of the secondary circuit protection fuse on the transformer Restore the fuse Glass fuse 10x20 F250mA 250V Che...

Страница 17: ...wer supply Prevent unauthorized personnel from being present in the intervention area Put signals to indicate that the machine is under maintenance Wear work clothes suits gloves shoes headgear suitab...

Страница 18: ...15 JB01 2 JB01 3 JB01 13 JB01 14 JB01 15 JB01 5 5 JB01 6 6 JB01 7 7 JB01 8 8 JB01 4 4 JB01 9 9 JB01 10 L10 JB01 11 L11 OPTYMA Control three phase 4 HP OPTYMA Control three phase 7 5 HP MODBUS B Power...

Страница 19: ...bonate screw cover 9 Auxiliary circuits transformer N B with inside a glass fuse 10 x 20 F250 mA 250 V 10 Connector for linking panel and the electronic card 11 Front panel 12 Electronic card 13 Elect...

Страница 20: ...t notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed All trademarks in this material are propert...

Отзывы: