FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
✭
=
General factory setting - also applying to spare part unit, H
H
H
H
H = HVAC setting, IIIII = Industrial setting, ( ) = parameter
window text. [ ] = value for use in communication via serial communication port
617 Fault log: Value
(F.LOG: VALUE)
Value:
[Index XX - XXX]
Function:
Array type parameter. This parameter makes it
possible to see at what current or voltage a given
trip occurred.
Description of choice:
Read out as one value.
Indication range: 0.0 - 999.9.
The fault log is reset after initialization (para. 620).
619 Reset of hours-run counter
(RESET RUN. HOUR)
Settings:
★
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero the hours-run counter (parameter
601).
Description of choice:
If
Reset
[1] has been selected the hours-run counter
of the FCM 300 is reset.
620 Operating mode (OPERATION MODE)
Settings:
★
Normal function (NORMAL OPERATION)
[0]
Control card test (CONTROL CARD TEST)
[2]
Initialization (INITIALIZE)
[3]
Function:
In addition to its normal function, this parameter can
be used for two different tests.
Also, all parameters (except parameters 603-605)
can be initialized.
621 Nameplate: FC type (FC TYPE)
Value:
Depends on unit
Function:
The key data of the unit can be read out via the
serial communication port.
Description of choice:
Type
indicates the unit size and basic function
concerned.
624 Nameplate: Software version no.
(SOFTWARE VERSION)
Value:
Depends on unit
Function:
The key data of the unit can be read out the serial
communication port.
Description of choice:
Software version
gives the version number.
Parameter Gr
oup 6: T
echnical functions
Description of choice:
Normal function
[0] is selected for normal operation
with the motor in the selected application.
Control card test
[2] is selected if control of the
analog and digital inputs, as well as the analog,
digital outputs and the +10 V control voltage is
desired.
A test connector with internal connections is
required for this test. Setup: Analog/digital output to
digital inputs 3, 4 and 5 and 10 V supply to analog/
digital input 2.
Initialization
[3] is selected if the factory setting of the
unit is desired without resetting parameters 500,
501 + 600 - 605. Initialization is active after power
up.
14-4
Содержание FCM305 56
Страница 4: ......
Страница 8: ...FCM 300 Series MG 03 B6 2G VLT is a registered Danfoss trademark...
Страница 16: ......
Страница 24: ......
Страница 46: ......
Страница 60: ......
Страница 74: ......
Страница 94: ......
Страница 110: ......
Страница 126: ......
Страница 131: ......
Страница 132: ......