FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
✭
=
General factory setting - also applying to spare part unit, H
H
H
H
H = HVAC setting, IIIII = Industrial setting,
( ) = display text [ ] = value for use in communication via serial communication port
Parameter Group 0: Operation & Display
This parameter disables/enables the local stop
function in question from the control panel.
This key is used when parameter 002 has been set
for
Remote control
[0] or
Local
[1].
Description of choice:
If
Disable
[0] is selected in this parameter, the
[STOP] key will be inactive.
NOTE!
If
Enable
is selected, the [STOP] key overrules all
Start commands.
015 Local jog (LOCAL JOGGING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the jog function can be enabled/
disabled on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the [JOG]
key will be inactive.
016 Local reversing
(LOCAL REVERSING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the reversing function can be
enabled/disabled on the control panel.
This key can only be used if parameter 002 has
been set to
Local operation
[1] and parameter 013
to
LCP control with open loop
[1] or
LCP control as
parameter 100
[3].
Description of choice:
If
Disable
[0] is selected in this parameter, the [FWD/
REV] key will be inactive.
See parameter 200.
017 Local reset of trip (LOCAL RESET)
Value:
Not possible (DISABLE)
[0]
✭
Possible (ENABLE)
[1]
Function:
In this parameter, the reset function can be
selected/removed from the keyboard.
This key can be used when parameter 002 has
been set for
Remote control
[0] or
Local control
[1].
Description of choice:
If
Disable
[0] is selected in this parameter, the
[RESET] key will be inactive.
NOTE!
Only select
Disable
[0] if an external reset signal has
been connected via the digital inputs.
8-7
Shift from
LCP digital control
and open loop
to
Remote control:
The selected configuration (parameter 100) will be
active. Shifts are effected without any abrupt
movement.
Shift from
Remote control to LCP control/as
parameter 100
or
LCP digital control/as parameter
100
.
The present reference will be maintained. If the
reference
signal is negative, the local reference will be set at
0.
Shift from
LCP control/as parameter 100
or
LCP
remote control as parameter 100
to
Remote control.
The reference will be replaced by the active
reference signal from the remote control.
014 Local stop (LOCAL STOP)
Value:
Not possible (DISABLE)
[0]
✭
Possible (ENABLE)
[1]
Function:
Содержание FCM305 56
Страница 4: ......
Страница 8: ...FCM 300 Series MG 03 B6 2G VLT is a registered Danfoss trademark...
Страница 16: ......
Страница 24: ......
Страница 46: ......
Страница 60: ......
Страница 74: ......
Страница 94: ......
Страница 110: ......
Страница 126: ......
Страница 131: ......
Страница 132: ......