Predefined application table for ERC 214
App
Mode
Description
Temperature
Defrost type
Defrost end
App 0
Cooling/
Heating
No predefined application
App 1
Cooling
Medium temperature ventilated refrigeration units
with timed natural defrost
(2 – 6 °C)
Natural
Time
App 2
Cooling
Medium temperature ventilated refrigeration units
with timed electrical defrost
(0 – 4 °C)
Electrical
Time
App 3
Cooling
Low temperature ventilated refrigeration units with
timed electrical defrost
(-26 – -20 °C)
Electrical
Time
App 4
Cooling
Medium temperature ventilated refrigeration units
with electrical defrost (by temperature)
(0 – 4 °C)
Electrical
Temperature
App 5
Cooling
Low temperature ventilated refrigeration units with
electrical defrost (by temperature)
(-26 – -20 °C)
Electrical
Temperature
App 6
Cooling/
Heating
No predefined application with simplified list of
parameters
Selection 1
covers normal temperature applications with natural defrost with stop on time.
Selection 2 and 3
covers respectively medium and low temperature applications with electrical defrost with stop on time.
Selection 4 and 5
covers respectively medium and low temperature applications with electrical defrost with stop on
defrost sensor “
S5
”.
Selection 6
covers applications where a reduced parameter list is recommended.
ERC 214 - APP 1
Sair
DI1
DO1
230 V AC
DO3
DO4
DI2
ERC 214 - APP 2-3
Sair
DI1
DO1
230 V AC
DO3
DO2
DO4
DI2
ERC 214 - APP 4-5
Sair
DI1
DO1
230 V AC
DO3
DO2
DO4
DI2
S5
2.5| Fan pulsating during compressor
OFF cycle
This is an energy saving feature. During compressor OFF cycle controller will run the fan with defined duty cycle to maintain
uniform temperature and delay the need of compressor switching ON