FR · ERC 21X user manual · DKRCC.ES.RL0.H3.02/520H9656 · ©Danfoss
Parameter name - ERC 214
Code
Min
Max
Unit App. 0
(Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Defrost
d--
Defrost method
no=no defrost, nAt=natural,
EL=electrical, gAS=hot gas
d01
no
gAS
EL
nAt
EL
EL
EL
EL
EL
Defrost stop temperature
d02
0.0
50.0
C/F
6.0
-
-
-
6.0
6.0
6.0
Defrost interval
d03
0
240
hours
8
6
8
12
8
12
8
Max defrost time
d04
0
480
min
30
45
15
15
30
30
30
Defrost delay at power up
(or DI signal)
d05
0
240.0
min
0
0
0
0
0
0
-
Drip delay
d06
0
60
min
0
0
0
0
0
0
5
Fan delay after defrost
d07
0
60
min
0
0
0
0
0
0
5
Fan start temperature
after defrost
d08
-50.0
0.0
C/F
-5.0
-
-
-
-5.0
-5.0
-
Fan during defrost
d09
oFF
on
on
on
on
on
on
on
on
Defrost stop sensor
configuration
non=time,
Air=Sair (air temperature),
dEF=S5 (defrost sensor)
d10
non
dEF
non
non
non
non
dEF
dEF
non
Compressor accumulated
runtime to start defrost
0=OFF
d18
0
96
hours
0
0
0
0
0
0
-
Defrost on demand
20.0=OFF
d19
0.0
20.0
K
20.0
-
-
-
20.0
20.0
-
Defrost delay after pull-down
0=OFF
d30
0
960
min
0
0
0
0
0
0
-
Fan control
F--
Fan at compressor cutout
FFc=fan follow compressor,
FAo=fan always ON,
FPL= fan pulsating
F01
FFc
FPL
FAo
FAo
FAo
FAo
FAo
FAo
FAo
Fan stop evaporator
temperature
50.0=OFF
F04
-50.0
50.0
C/F
50.0
-
-
-
50.0
50.0
-
Fan ON cycle
F07
0
15
min
2
2
2
2
2
2
2
Fan OFF cycle
F08
0
15.0
min
2
2
2
2
2
2
2
Compressor
c--
Compressor minimum ON time
C01
0
30
min
0
0
0
0
0
0
0
Compressor minimum OFF time
C02
0
30
min
2
2
2
2
2
2
2
Compressor OFF delay
at door open
C04
0
15
min
0
0
0
0
0
0
1
Zero crossing selection
C70
no
yES
yES
yES
yES
yES
yES
yES
yES
Note: hidden parameters are greyed out