Parameter name - ERC 214

Code

Min

Max

Unit App. 0

(Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6

Defrost

d--

Defrost method

no=no defrost, nAt=natural, 
EL=electrical, gAS=hot gas

d01

no

gAS

EL

nAt

EL

EL

EL

EL

EL

Defrost stop temperature

d02

0.0

50.0

C/F

6.0

-

-

-

6.0

6.0

6.0

Defrost interval

d03

0

240

hours

8

6

8

12

8

12

8

Max defrost time

d04

0

480

min

30

45

15

15

30

30

30

Defrost delay at power up 

(or DI signal)

d05

0

240.0

min

0

0

0

0

0

0

-

Drip delay

d06

0

60

min

0

0

0

0

0

0

5

Fan delay after defrost

d07

0

60

min

0

0

0

0

0

0

5

Fan start temperature 

after defrost

d08

-50.0

0.0

C/F

-5.0

-

-

-

-5.0

-5.0

-

Fan during defrost

d09

oFF

on

on

on

on

on

on

on

on

Defrost stop sensor

 

configuration 

non=time, 

Air=Sair (air temperature), 
dEF=S5 (defrost sensor)

d10

non

dEF

non

non

non

non

dEF

dEF

non

Compressor accumulated 

runtime to start defrost 

0=OFF

d18

0

96

hours

0

0

0

0

0

0

-

Defrost on demand 

20.0=OFF

d19

0.0

20.0

K

20.0

-

-

-

20.0

20.0

-

Defrost delay after pull-down 

0=OFF

d30

0

960

min

0

0

0

0

0

0

-

Fan control

F--

Fan at compressor cutout

FFc=fan follow compressor, 
FAo=fan always ON, 
FPL= fan pulsating

F01

FFc

FPL

FAo

FAo

FAo

FAo

FAo

FAo

FAo

Fan stop evaporator 

temperature 

50.0=OFF

F04

-50.0

50.0

C/F

50.0

-

-

-

50.0

50.0

-

Fan ON cycle

F07

0

15

min

2

2

2

2

2

2

2

Fan OFF cycle

F08

0

15.0

min

2

2

2

2

2

2

2

Compressor

c--

Compressor minimum ON time

C01

0

30

min

0

0

0

0

0

0

0

Compressor minimum OFF time

C02

0

30

min

2

2

2

2

2

2

2

Compressor OFF delay 

at door open

C04

0

15

min

0

0

0

0

0

0

1

Zero crossing selection

C70

no

yES

yES

yES

yES

yES

yES

yES

yES

Note: hidden parameters are greyed out

Содержание ERC 211

Страница 1: ...nfoss com erc User manual ERC 21X temperature controllers series 4 push buttons a big display and an intuitive menu structure ensure superior ease of use ERC 21X smart multipurpose refrigeration contr...

Страница 2: ...3 Installation steps 11 4 4 Electrical connection diagram 12 4 4 1 ERC 211 connection diagram 12 4 4 2 ERC 213 connection diagram 12 4 4 3 ERC 214 connection diagram 12 4 5 Power supply 13 4 6 Sensors...

Страница 3: ...3 FR ERC 21X user manual DKRCC ES RL0 H3 02 520H9656 Danfoss...

Страница 4: ...s other commercial refrigeration applications 1 2 General Description ERC21X controller comes with four push buttons a big display easy and intuitive menu structure and pre defined applications ensure...

Страница 5: ...ions as mentioned under menu code o02 Input 4 digital input which can be configured to various functions as mentioned under menu code o37 1 3 3 ERC 214 ERC 214 has four relays outputs and four inputs...

Страница 6: ...rly warning through condenser alarm and if temperature rises further it will switch the compressor OFF If the temperature measured by the condenser sensor Sc is reaching the set pre alarm limit a alar...

Страница 7: ...and AP6 in case of ERC213 ERC214 Pre defined application table of ERC 211 controller App Mode Description Temperature Defrost type Defrost end App 0 Cooling Heating No predefined application App 1 Co...

Страница 8: ...al defrost by temperature 0 4 C Electrical Temperature App 5 Cooling Low temperature ventilated refrigeration units with electrical defrost by temperature 26 20 C Electrical Temperature App 6 Cooling...

Страница 9: ...l defrost by temperature 26 20 C Electrical Temperature App 6 Cooling Heating No predefined application with simplified list of parameters Selection 1 covers normal temperature applications with natur...

Страница 10: ...vanic isolated low voltage regulated power supply Rated power Less than 0 7 W Inputs 4 inputs 2 analogue 1 analogue digital and 1 digital Allowed sensor types NTC 5000 Ohm at 25 C Beta value 3980 at 2...

Страница 11: ...3 Installation steps Place the wired controller in the slot and ensure rubber sealing is resting properly on the mounting surface Slide the mounting clips along the rails of the rear plastic from the...

Страница 12: ...e product code number GND TX RX 5V 4 4 2 ERC 213 connection diagram DO1 1 2 Sair S5 Sc DI1 DI2 DO2 DO3 GND GND Programming key EKA 183A 3L 4N 5 6 7 8 9 10 15 16 17 18 11 12 13 14 Power supply accordin...

Страница 13: ...r up STEP 1 power on STEP 2 select the quick configuration menu Within 30 seconds of power on press BACK for 3 seconds The main switch r12 is automatically set to OFF STEP 3 select pre installed appli...

Страница 14: ...automatically shows the o36 parameter to configure DO4 output Available only in 4 relays model Select light Lig or alarm ALA as per the application and press SET to confirm The display returns to nor...

Страница 15: ...point temperature UP DOWN change the temperature setpoint in setting mode the setpoint flashes SET save the temperature setpoint 5 6 Initiate a manual defrost DEFROST press for 3 seconds to initiate a...

Страница 16: ...temperature reaches the set point differetial In case of heating application heater will cut in when the temperature reaches the set point differential r02 Minimum set point limitation The minimum al...

Страница 17: ...r high block limit If the condenser temperature continues to increase above the A37 limit and reaches this temperature limit condenser block alarm is raised and compressor is stopped It is restricted...

Страница 18: ...compressor runtime is less than the set value during the define defrost interval d03 defrost will be triggered based on the defrost interval d03 This feature is disabled when this parameter is set to...

Страница 19: ...ited EAL external alarm Alarm will be given when the input is short circuited dEF defrost Defrost is initiated when the input is short circuited Edge triggering is used Defrost exit can take place by...

Страница 20: ...eference r00 when the input is short circuited EAL external alarm Alarm will be given when the input is short circuited dEF defrost Defrost is initiated when the input is short circuited Edge triggeri...

Страница 21: ...t and deactivated when DI1 port is short circuit P74 DI2 input polarity no normally open associated functionality is activated when DI2 port is short circuit The associated function is deactivated whe...

Страница 22: ...erature calibration r09 20 0 20 0 K 0 0 0 0 0 0 0 0 0 0 Main switch 1 service 0 OFF 1 ON r12 1 1 1 1 1 1 1 Night set back offset temperature during night mode r13 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 T...

Страница 23: ...nimum ON time C01 0 30 min 0 0 0 0 0 0 0 Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 0 Compressor OFF delay at door open C04 0 15 min 0 0 0 0 0 1 Zero crossing selection C70 no yES yES yES yE...

Страница 24: ...ble P76 no yES no no no no no Readouts u Controller status S0 cooling ON Heating ON S2 wait for compressor ON time to elapse S3 wait for compressor OFF time to elapse restart time S4 drip OFF delay af...

Страница 25: ...2 1 1 1 1 1 1 1 1 Night set back offset temperature during night mode r13 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Thermostat reference displacement offset temperature r40 50 0 50 0 K 0 0 0 0 0 0 0 0 0...

Страница 26: ...p sensor configuration non time Air Sair air temperature dEF S5 defrost sensor d10 non dEF non non non non dEF dEF non Compressor accumulated runtime to start defrost 0 OFF d18 0 96 hours 0 0 0 0 0 0...

Страница 27: ...1 0 1 0 1 0 1 0 1 0 1 0 1 Relay 1 counter 1 count 100 cycles of operation o23 0 999 0 0 0 0 0 0 Relay 2 counter 1 count 100 cycles of operation o24 0 999 0 0 0 0 0 0 Relay 3 counter 1 count 100 cycle...

Страница 28: ...pse restart time S4 drip OFF delay after defrost S10 cooling stop S11 cooling stopped by thermostat heating OFF S14 defrosting state S15 fandelaystateafterdefrost S17 door open DI input S20 emergency...

Страница 29: ...0 0 Main switch 1 service 0 OFF 1 ON r12 1 1 1 1 1 1 1 1 Night set back offset temperature during night mode r13 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Thermostat reference displacement offset temper...

Страница 30: ...p sensor configuration non time Air Sair air temperature dEF S5 defrost sensor d10 non dEF non non non non dEF dEF non Compressor accumulated runtime to start defrost 0 OFF d18 0 96 hours 0 0 0 0 0 0...

Страница 31: ...nt 100 cycles of operation o23 0 999 0 0 0 0 0 0 Relay 2 counter 1 count 100 cycles of operation o24 0 999 0 0 0 0 0 0 Relay 3 counter 1 count 100 cycles of operation o25 0 999 0 0 0 0 0 0 Relay 4 cou...

Страница 32: ...time S4 drip OFF delay after defrost S10 cooling stop S11 cooling stopped by thermostat heating OFF S14 defrosting state S15 fandelaystateafterdefrost S17 door open DI input S20 emergency cooling S25...

Страница 33: ...eck r r96 Check r r97 Wrong temperature displayed Wrong type of sensor selected Check cFg o06 8 Ordering Type Description Relay Code no ERC 211 RED LED 115 V Single Multi Pack 1 080G3290 ERC 211 RED L...

Страница 34: ...34 FR ERC 21X user manual DKRCC ES RL0 H3 02 520H9656 Danfoss NOTES...

Страница 35: ...35 FR ERC 21X user manual DKRCC ES RL0 H3 02 520H9656 Danfoss NOTES...

Страница 36: ...foss Produced by AZ 2015 02 Simple temperature and defrost management countless functions and benefits ERC 21X is a smart multipurpose refrigeration controller designed to fulfill today s requirements...

Отзывы: