24
FR · ERC 21X user manual · DKRCC.ES.RL0.H3.02/520H9656 · ©Danfoss
Parameter name - ERC 211
Code
Min
Max
Unit
App. 0
(Def.) App. 1 App. 2 App. 3 App. 4 App. 5
Relay 1 counter
(1 count=100 cycles of
operation)
o23
0
999
0
0
0
0
0
-
Predefined applications
o61
AP0
AP5
AP0
AP1
AP2
AP3
AP4
-
Save settings as factory
WARNING: the earlier factory
settings are overwritten
o67
no
yES
no
no
no
no
no
-
Display at defrost
Air=actual air temperature,
FrE=freezed temperature,
-d-="-d-" is displayed
o91
Air
-d-
-d-
-
-d-
-d-
-
-d-
Polarity
P--
DI1 input polarity
nc=normally closed,
no=normally open
P73
nc
no
no
no
no
no
no
no
Keyboard lock enable
P76
no
yES
no
no
no
no
no
-
Readouts
u--
Controller status
S0=cooling ON/Heating ON,
S2=wait for compressor ON time
to elapse,
S3=wait for compressor OFF time
to elapse-restart time,
S4=drip OFF delay after defrost,
S10=cooling stop
S11=cooling stopped by
thermostat/heating OFF,
S14=defrosting state,
S15=fan delay state after defrost,
S17=door open (DI input),
S20=emergency cooling,
S25=manual control of outputs,
S30=continous cycle/Pull-down,
S32=delay of outputs at power up
u00
S0
S32
--
Air temperature (Sair)
u01
-100.0
200.0
C/F
---
Read the present regulation
reference
u02
-100.0
200.0
C/F
---
DI1 input
u10
oFF
on
---
Status of night operation
u13
oFF
on
---
Condenser temperature (Sc)
U09
-100.0
200.0
C/F
---
Compressor relay status
u58
oFF
on
---
Firmware version readout
u80
000
999
---
Note: hidden parameters are greyed out