Menu code Parameter description

d04

Maximum defrost time

This parameter defines the defrost time when it is time based defrost. In case of temperature based defrost this 
is treated as safety time to stop the defrost if it is not terminated based on the temperature.

d05

Defrost delay at power up or DI signal

This parameter decides the time offset when the defrost is triggered by digital inputs or during power up. 
This function is only relevant if you have several refrigeration appliances or groups where you want the defrost 
to be staggered in relation to one another.

d06

Drip-OFF time

This parameter defines the time delay to start the compressor after defrost heater being switched OFF. 
This delay is generally provided to ensure all water droplets on the evaporator drips off before starting the 
refrigeration cycle.

d07

Fan delay after defrost

Defines how long the delay is between the start of the compressor and the fan after defrost cycle.

d08

Fan start temperature after defrost

This only applies if an evaporator temperature sensor is fitted. 
This parameter determines at what evaporator temperature the fan will start after a defrost cycle is complete. 
If the time set in “d07” occurs before the temperature set in “d08”, the fan will start in line with “d07”. 
If the temperature set in “d08” occurs first, then the fan will start in line with “d08”. 

d09

Fan during defrost

This parameter is to define whether fan is to operate during defrost or not.

d10

Defrost stop sensor

This parameter is to define which sensor has to be used to exit/terminate the defrost.

non=none, defrost is based on time
Air=Sair sensor
dEF=S5 (defrost) sensor

d18

Compressor accumulated runtime to start defrost

When the accumulated compressor runtime is equal to the value set in this Parameter, defrost will be triggered. 
If the compressor runtime is less than the set value during the define defrost interval “d03”, defrost will be 
triggered based on the defrost interval “d03”. This feature is disabled when this parameter is set to zero.

d19

Defrost on demand

The controller will constantly monitor the “S5” temperature to estimate the ice buildup. 
In between two defrosts, if the “S5” temperature become lower than the value defined here controller will 
initiate the defrost on demand. 
This feature is disabled when this parameter is set to 20. This function can only be used in 1:1 systems.

d30

Defrost delay after pull down

This parameter defines the time delay to start the defrost after pull down cycle. 
This has to ensure defrost doesn’t happen immediately after pull down cycle.

F--

Fan control

F01

Fan at compressor cut-out

This parameter define the fan operation during compressor OFF cycle.

FAo=fan always ON
FFC=fan follow compressor
FPL=fan Pulsating

F04

Fan stop evaporating temperature

This parameter defines the maximum evaporator temperature at which the Fan must switch OFF. 
If the defrost sensor registers a higher temperature than the one set here, the fans will be stopped to avoid the 
warm air circulation in the cabinet.

F07

Fan ON cycle

This parameter is applicable only when the Fan at Compressor cut out “F01” is set to Fan Pulsating mode. 
The Fan pulsating ON time will be as per the time set in this parameter.

F08

Fan OFF cycle

This parameter is applicable only when the Fan at Compressor cut out “F01” is set to Fan Pulsating mode. 
The Fan pulsating OFF time will be as per the time set in this parameter.

 c--

Compressor

C01

Compressor minimum ON time

This parameter determines the minimum number of minutes the compressor must run before a cut-out can 
take effect based on temperature. This is to avoid sudden switching ON and OFF of the compressor.

C02

Compressor minimum OFF time

This parameter determines the minimum number of minutes the compressor must switched OFF before a 
cut-in can take effect based on temperature. This is to avoid sudden switching OFF and ON of the compressor.

Содержание ERC 211

Страница 1: ...nfoss com erc User manual ERC 21X temperature controllers series 4 push buttons a big display and an intuitive menu structure ensure superior ease of use ERC 21X smart multipurpose refrigeration contr...

Страница 2: ...3 Installation steps 11 4 4 Electrical connection diagram 12 4 4 1 ERC 211 connection diagram 12 4 4 2 ERC 213 connection diagram 12 4 4 3 ERC 214 connection diagram 12 4 5 Power supply 13 4 6 Sensors...

Страница 3: ...3 FR ERC 21X user manual DKRCC ES RL0 H3 02 520H9656 Danfoss...

Страница 4: ...s other commercial refrigeration applications 1 2 General Description ERC21X controller comes with four push buttons a big display easy and intuitive menu structure and pre defined applications ensure...

Страница 5: ...ions as mentioned under menu code o02 Input 4 digital input which can be configured to various functions as mentioned under menu code o37 1 3 3 ERC 214 ERC 214 has four relays outputs and four inputs...

Страница 6: ...rly warning through condenser alarm and if temperature rises further it will switch the compressor OFF If the temperature measured by the condenser sensor Sc is reaching the set pre alarm limit a alar...

Страница 7: ...and AP6 in case of ERC213 ERC214 Pre defined application table of ERC 211 controller App Mode Description Temperature Defrost type Defrost end App 0 Cooling Heating No predefined application App 1 Co...

Страница 8: ...al defrost by temperature 0 4 C Electrical Temperature App 5 Cooling Low temperature ventilated refrigeration units with electrical defrost by temperature 26 20 C Electrical Temperature App 6 Cooling...

Страница 9: ...l defrost by temperature 26 20 C Electrical Temperature App 6 Cooling Heating No predefined application with simplified list of parameters Selection 1 covers normal temperature applications with natur...

Страница 10: ...vanic isolated low voltage regulated power supply Rated power Less than 0 7 W Inputs 4 inputs 2 analogue 1 analogue digital and 1 digital Allowed sensor types NTC 5000 Ohm at 25 C Beta value 3980 at 2...

Страница 11: ...3 Installation steps Place the wired controller in the slot and ensure rubber sealing is resting properly on the mounting surface Slide the mounting clips along the rails of the rear plastic from the...

Страница 12: ...e product code number GND TX RX 5V 4 4 2 ERC 213 connection diagram DO1 1 2 Sair S5 Sc DI1 DI2 DO2 DO3 GND GND Programming key EKA 183A 3L 4N 5 6 7 8 9 10 15 16 17 18 11 12 13 14 Power supply accordin...

Страница 13: ...r up STEP 1 power on STEP 2 select the quick configuration menu Within 30 seconds of power on press BACK for 3 seconds The main switch r12 is automatically set to OFF STEP 3 select pre installed appli...

Страница 14: ...automatically shows the o36 parameter to configure DO4 output Available only in 4 relays model Select light Lig or alarm ALA as per the application and press SET to confirm The display returns to nor...

Страница 15: ...point temperature UP DOWN change the temperature setpoint in setting mode the setpoint flashes SET save the temperature setpoint 5 6 Initiate a manual defrost DEFROST press for 3 seconds to initiate a...

Страница 16: ...temperature reaches the set point differetial In case of heating application heater will cut in when the temperature reaches the set point differential r02 Minimum set point limitation The minimum al...

Страница 17: ...r high block limit If the condenser temperature continues to increase above the A37 limit and reaches this temperature limit condenser block alarm is raised and compressor is stopped It is restricted...

Страница 18: ...compressor runtime is less than the set value during the define defrost interval d03 defrost will be triggered based on the defrost interval d03 This feature is disabled when this parameter is set to...

Страница 19: ...ited EAL external alarm Alarm will be given when the input is short circuited dEF defrost Defrost is initiated when the input is short circuited Edge triggering is used Defrost exit can take place by...

Страница 20: ...eference r00 when the input is short circuited EAL external alarm Alarm will be given when the input is short circuited dEF defrost Defrost is initiated when the input is short circuited Edge triggeri...

Страница 21: ...t and deactivated when DI1 port is short circuit P74 DI2 input polarity no normally open associated functionality is activated when DI2 port is short circuit The associated function is deactivated whe...

Страница 22: ...erature calibration r09 20 0 20 0 K 0 0 0 0 0 0 0 0 0 0 Main switch 1 service 0 OFF 1 ON r12 1 1 1 1 1 1 1 Night set back offset temperature during night mode r13 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 T...

Страница 23: ...nimum ON time C01 0 30 min 0 0 0 0 0 0 0 Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 0 Compressor OFF delay at door open C04 0 15 min 0 0 0 0 0 1 Zero crossing selection C70 no yES yES yES yE...

Страница 24: ...ble P76 no yES no no no no no Readouts u Controller status S0 cooling ON Heating ON S2 wait for compressor ON time to elapse S3 wait for compressor OFF time to elapse restart time S4 drip OFF delay af...

Страница 25: ...2 1 1 1 1 1 1 1 1 Night set back offset temperature during night mode r13 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Thermostat reference displacement offset temperature r40 50 0 50 0 K 0 0 0 0 0 0 0 0 0...

Страница 26: ...p sensor configuration non time Air Sair air temperature dEF S5 defrost sensor d10 non dEF non non non non dEF dEF non Compressor accumulated runtime to start defrost 0 OFF d18 0 96 hours 0 0 0 0 0 0...

Страница 27: ...1 0 1 0 1 0 1 0 1 0 1 0 1 Relay 1 counter 1 count 100 cycles of operation o23 0 999 0 0 0 0 0 0 Relay 2 counter 1 count 100 cycles of operation o24 0 999 0 0 0 0 0 0 Relay 3 counter 1 count 100 cycle...

Страница 28: ...pse restart time S4 drip OFF delay after defrost S10 cooling stop S11 cooling stopped by thermostat heating OFF S14 defrosting state S15 fandelaystateafterdefrost S17 door open DI input S20 emergency...

Страница 29: ...0 0 Main switch 1 service 0 OFF 1 ON r12 1 1 1 1 1 1 1 1 Night set back offset temperature during night mode r13 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Thermostat reference displacement offset temper...

Страница 30: ...p sensor configuration non time Air Sair air temperature dEF S5 defrost sensor d10 non dEF non non non non dEF dEF non Compressor accumulated runtime to start defrost 0 OFF d18 0 96 hours 0 0 0 0 0 0...

Страница 31: ...nt 100 cycles of operation o23 0 999 0 0 0 0 0 0 Relay 2 counter 1 count 100 cycles of operation o24 0 999 0 0 0 0 0 0 Relay 3 counter 1 count 100 cycles of operation o25 0 999 0 0 0 0 0 0 Relay 4 cou...

Страница 32: ...time S4 drip OFF delay after defrost S10 cooling stop S11 cooling stopped by thermostat heating OFF S14 defrosting state S15 fandelaystateafterdefrost S17 door open DI input S20 emergency cooling S25...

Страница 33: ...eck r r96 Check r r97 Wrong temperature displayed Wrong type of sensor selected Check cFg o06 8 Ordering Type Description Relay Code no ERC 211 RED LED 115 V Single Multi Pack 1 080G3290 ERC 211 RED L...

Страница 34: ...34 FR ERC 21X user manual DKRCC ES RL0 H3 02 520H9656 Danfoss NOTES...

Страница 35: ...35 FR ERC 21X user manual DKRCC ES RL0 H3 02 520H9656 Danfoss NOTES...

Страница 36: ...foss Produced by AZ 2015 02 Simple temperature and defrost management countless functions and benefits ERC 21X is a smart multipurpose refrigeration controller designed to fulfill today s requirements...

Отзывы: