27
FR · ERC 21X user manual · DKRCC.ES.RL0.H3.02/520H9656 · ©Danfoss
Parameter Name - ERC 213
Code
Min
Max
Unit App. 0
(Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Others
o--
Delay of outputs
at startup
o01
0
600
min
5
5
5
5
5
5
5
DI1 configuration
oFF=not used,
Sdc=status display output,
doo=door alarm with resumption,
doA=door alarm without resumption,
SCH=main switch, nig=day/ night
mode, rFd=reference displacement,
EAL=external alarm, dEF=defrost,
Pud=pull-down,
Sc=condenser sensor
o02
oFF
Sc
oFF
oFF
oFF
oFF
oFF
oFF
oFF
Serial address
o03
0
247
0
0
0
0
0
0
-
Password
o05
no
999
no
no
no
no
no
no
no
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K,
Ptc=PTC, Pt1=Pt1000
o06
n5
Pt1
n10
n10
n10
n10
n10
n10
-
Display resolution
0.1=steps of 0.1 °C
0.5=steps of 0.5 °C,
1.0=steps of 1.0 °C
o15
0.1
1.0
0.1
0.1
0.1
0.1
0.1
0.1
0.1
Relay 1 counter
(1 count=100 cycles of
operation)
o23
0
999
0
0
0
0
0
0
-
Relay 2 counter
(1 count=100 cycles of
operation)
o24
0
999
0
0
0
0
0
0
-
Relay 3 counter
(1 count=100 cycles of
operation)
o25
0
999
0
0
0
0
0
0
-
DI2 configuration
oFF=not used,
Sdc=status display output,
doo=door alarm with resumption,
doA=door alarm without resumption,
SCH=main switch,
nig=day/night mode,
rFd=reference displacement,
EAL=external alarm, dEF=defrost,
Pud=pull-down
o37
oFF
Pud
oFF
oFF
oFF
oFF
oFF
oFF
oFF
Light control
on=always on, dAn=day/night,
doo=based on door action
o38
on
doo
on
on
on
on
on
on
on
o61
AP0
AP6
AP0
AP1
AP2
AP3
AP4
AP5
-
Save settings as factory
WARNING: the earlier factory
settings are overwritten
o67
no
yES
no
no
no
no
no
no
-
DO2 config
(dEF=defrost; ALA=alarm)
o71
dEF
ALA
dEF
ALA
dEF
dEF
dEF
dEF
dEF
Display at defrost
Air=actual air temperature,
FrE=freezed temperature,
-d-="-d-" is displayed
o91
Air
-d-
-d-
-d-
-d-
-d-
-d-
-d-
-d-
Note: hidden parameters are greyed out