BC-HM
VI.72.M4.02
Danfoss 11/97
5
Electrical connections and
wiring diagram
Connection to 230 VAC -
(terminals 13-24)
The control must be connected using the
terminal strips with screw terminals.
Up to 3 x 1.5 mm² or corresponding
wires can be connected in each
terminal. The terminal strips are coded
to prevent terminal strips with mains
voltage being connected to sensor
terminals.
Terminal
Load
Neutral (N) - 230 V~
13
Phase (L) - 230 V~
14
16 (close)
8(2)A 250V~
Reversible gear motor 230 V~, AMB, AMV etc.
17 (open)
8(2)A 250V~
Relay output R1 - 230 V~ (NC)
21 - 22
8(2)A 250V~
Relay output R2 - 230 V~ (NC)
23 - 24
8(2)A 250V~
Connections for sensors, etc. -
safety voltage (terminals 1 - 12)
Sensor mounting is described in the
instructions enclosed with the product.
Wire cross-section: min. 0.4 mm²
Total length of all sensor and BUS
wires: max. 150 metres.
Type
Terminal
S1
flow/duct (PI circuit)
ESMA/B/C/U
10 - 11
storage tank upper sensor
ESMB/U
S2
7 - 9
room sensor (P circuit)
ESMR
S3
frost protection sensor
ESMB/U/T
11 - 12
S4
return temperature sensor
ESMA/B/C/U
4 - 6
S5
external setpoint
ESME
4 - 5
storage tank lower sensor
ESMB/U
S6
8 - 9
compensation sensor
ESMR/T
External time switch/override
ECA 9010
3 - 4
Communication BUS
1 - 2
Note!
Wire resistance can give measurement
error. A resistance of 4 ohm
corresponds to a temperature increase
of about 1 degree.
Содержание EPU 2370
Страница 24: ...24 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 A 1 B and 1 C...
Страница 28: ...28 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 D and 1 E...
Страница 32: ...32 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 2 A and 2 B...
Страница 36: ...36 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System type 3...
Страница 40: ...40 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 4 A and 4 B...