BC-HM
VI.72.M4.02
Danfoss 11/97
23
System 1-C - Hot-water-service storage tank with secondary mixing
Operating
Relay 1
Relay 2
condition
Standby
0
0
Reduced
0
time switch
Normal
1*)
time switch
Frost
1
1
Control principle for 1-C
PI control of temperature at S1 in tap
circuit. Temperature held constant by
motor valve control M in secondary
circuit.
Note:
The relay status in different operating
conditions is shown in the table.
*
)
On changing over from normal to
reduced, R1 is delayed 3 minutes.
0 = open relay contact
1 = closed relay contact