BC-HM
VI.72.M4.02
Danfoss 11/97
29
Row
←
(–) Column 0-4 (+)
→
0-9
0
1
2
3
4
0
P0.0
P0.1
P0.2
P0.3
P0.4
Status
Software
System
Time switch
Slave
generation
number
channel select
adress
F: 1
F: 0.0
F: 15
1
P1.0
P1.1
P1.2
P1.4
S1 actual
S1 reference
Valve
Motor
charging
charging
function
constant
temperature
temperature
F: 1
F: 17 s
2
P2.0
P2.1
P2.2
P2.3
P2.4
S2 actual
S2 reference
S1ref-T.cut-out
Anti-bacteria
X
p
- propor-
storage tank
cut-in
F: 5 K
function
tional band
temperature
temperature
F: - - (OFF)
F: 50 K
3
P3.0
P3.1
P3.4
S3 actual
S3 reference
T
n
- integra-
temperature
frost
tion time
temperature
F: 15 s
F: 2 °C
4
P4.0
P4.1
P4.2
P4.4
S4 actual
S4 return limit
Return limit
N
z -
-
return temp.
max./min.
amplification
neutral zone
F: 40 °C
F: -4 times
F: 3 K
5
P5.0
P5.3
S5 actual
S5 scale mid-
ext. setpoint
point for ext.
setpoint
F: 50 °C
6
P6.0
P6.1
P6.2
S6 actual
S6 reference
Temp. diff.
temperature
cut-out
T
cut-out
- T
cut-in
temperature
F: 5 K
7
P7.0
P7.1
S1 actual hot-
Alarm code
water-service
temperature
8
P8.0
Normal hot
water-service
temperature
Settings in connection with sensors S3 and S4
F: 50 °C
and ext- setpoint S5
9
P9.0
F:
Factory setting
Reduced hot
water-service
temperature
F: 40 °C
Factory settings - System types 1-D and 1-E
For further information see page 15 to 21.
Содержание EPU 2370
Страница 24: ...24 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 A 1 B and 1 C...
Страница 28: ...28 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 D and 1 E...
Страница 32: ...32 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 2 A and 2 B...
Страница 36: ...36 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System type 3...
Страница 40: ...40 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 4 A and 4 B...