BC-HM
VI.72.M4.02
Danfoss 11/97
39
Notes
- System 4-B is registered
automatically when sensor S2 is
connected. The necessary settings
become visible in the display
(registered when the unit is switched
on).
- Load-dependent compensation is
possible by connecting sensor S6.
Two independent compensation
curves can be set. Curves must be
set in P6.2 and P6.3 in P7.2 and P7.3
respectively.
- With reduced temperature, total stop
function in P1.2 has the following
influence:
0
Control according to reduced
setpoint (P9.0). Pump constantly
cut in.
1
Valve closes and pump stops
until room temperature falls to the
required temperature. Valve then
opens and pump starts until room
temperature has risen 1 degree.
- Relay status for different operating
situations with this system are as
follows:
Operating
Relay 1
Relay 2
condition
Standby
0
0
P1.2 = 0
1
time switch**)
Reduced
P1.2 = 1
0
time switch**)
Normal
1*)
time switch**)
Frost
1
1
*
)
On changing over from normal to
reduced operation, R1 is delayed 3
minutes.
**
)
Relay contact R2 open with reduced
temperature.
0 = open relay contact
1 = closed relay contact
Содержание EPU 2370
Страница 24: ...24 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 A 1 B and 1 C...
Страница 28: ...28 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 1 D and 1 E...
Страница 32: ...32 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 2 A and 2 B...
Страница 36: ...36 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System type 3...
Страница 40: ...40 VI 72 M4 02 Danfoss 11 97 BC HM Wiring diagram System types 4 A and 4 B...