The maximum distance between the copper tape or the shield (braid) of the cable and the
cable lug or the conductor (which ever is closer), is 10 mm.
Do not remove the cable sheath completely at this point and do not cut the braid screen of
the cable!
Cut length of the cable sheath
3. Insert the cable to the cable gland with slight turning motion. This helps the cable to go through the
spring inside the cable gland. Push the cable gland against the sheath of the cable as shown in Figure
below.
Cable to the gland assembly
4. After the cable gland is in place remove the length A piece of the sheath and cut the braid screen
(cover) from 10 mm (distance C) from the gland bottom as shown in Figure below.
Make sure that the cable gland spring is against the cable sheath (that is protected with
copper tape) before cutting the braid screen.