This Chapter describes how to assemble screened power cables to the electric machine. See the cable
glands recommendations from the Table below. Cable gland assembly instruction can also be found from
PFLITSCH gland catalog available from
Use correct type of gland for different cable diameters. These are shown in the Table below.
Cable gland alternatives
Cable diameter
Cable gland
35 mm
2
50 mm
2
70 mm
2
Pflitcsh blueglobe mstri225
x
x
x
Pflitcsh blueglobe mstri232
x
x
Blueglobe cable gland tightening torques
Metric thread
Nominal torque
M10x1,0
3,0 Nm
M12x1,5
5,0 Nm
M16x1,5
8,0 Nm
M20x1,5
10,0 Nm
M25x1,5
15,0 Nm
M32x1,5
15,0 Nm
M40x1,5
20,0 Nm
M50x1,5
30,0 Nm
M63x1,5
35,0 Nm
M75x1,5
80,0 Nm
M85x2,0
100,0 Nm
1. Remove the small hexagonal piece from the BlueGlobe-sealing insert as shown in Figure below.
BlueGlobe-sealing
2. Cut the cable sheath at the distance A from the end of the cable, see Figure below. Pull the cut part of
the sheath partly (length B is from 10 to 15 mm) off the cable as shown in the Figure. The distance A
depends of the length of the cable lug used. Measure with the cable lug that is used and cut to
suitable length.
Install two layers of copper tape on the cable so that the distance B is covered. Use 3M
™
Copper Foil Tape 1181 or similar.
User Guide
EM-PMI540-T4000
Installation
©
Danfoss | April 2023
BC265857716810en-000202 | 37