Troubleshooting chart (continued)
Symptom
Possible cause
Action
Electric machine does not work
properly or the performance is
poor
Wrong electric machine parameters in
the inverter.
Check and correct the electric machine parameters from the inverter.
Demagnetization of magnets due to
overheating.
Measure the winding resistance, refer to manufacturer data. Replace the
electric machine if necessary.
Bearing fault.
Check the bearings, lubrication and conditions.
Insulation fault.
Measure the insulation resistance, refer to the manufacturer limits. See
Chapter
. Replace the electric machine if
necessary.
Anti-condensation heater failure
The heater element is faulty.
Measure the resistance of the heater element. See Chapter
condensation heater connections
on page 51. If the heater is faulty,
contact Danfoss.
Temperature measurement failure The PT100 sensor is faulty.
Measure the resistance of the PT100 sensor, see Chapter
. If the sensor is faulty, read out the signal from
another sensor. Contact Danfoss. See Chapter
.
User Guide