User Guide | Liquid level controller, EKE 347
© Danfoss | DCS (ADAP-KOOL®) | 2016-04
DKRCI.PD.RP0.A4.02 | 6
Setup & service menu - COMMISSIONING
Parameter
Options
Default
values
Reference
Main switch
On, Off
Off
Liquid level setpoint
0 - 100%
50.0%
Operation mode
Master, IO, Slave
Master
Alarm setup
Lower level limit
0 - 100%
15%
Upper level limit
0 - 100%
85%
Level alarm mode
Time, Hysteresis
Time
Lower delay
0 - 999 sec
10 sec
Upper delay
0 - 999 sec
50 sec
Lower level hysteresis
0-20 %
3%
Upper level hysteresis
0-20 %
5%
Function common alarm
Not follow; Follow up; Follow low; Follow all
Not follow
Oscillation detect band
0 - 100%
100%
Oscillation detect timeout
2 - 30 min
20 min
Force pump OFF in stop mode
Yes / No
No
IO Lower level limit
0 - 100%
5%
IO Upper level limit
0 - 100%
95%
IO Lower level hysteresis
0-20 %
3%
IO Upper level hysteresis
0-20 %
3%
IO Lower delay
0 - 999 sec
10 sec
IO Upper delay
0 - 999 sec
50 sec
IO Level limit
0 - 100%
50%
IO Level delay
0 - 999 sec
10 sec
IO Level hysteresis
0-20 %
3%
IO Level action
Falling,Rising
Falling
Control
Control Method
On/Off ,P, PI
PI
Regulating principle
Low, High
Low
P-band
5 - 200%
30.0%
Integration time Tn
60 - 600 sec
400 sec
Neutral zone
0 - 25%
2.0%
Difference
0,5-25%
2%
Period time for AKV/AKVA
3-15 sec
6 sec
Minimum OD
0 - 99%
0%
Maximum OD
1 - 100%
100%
Display
Language
EN,CN,PT,RU,SP,FR,IT, GER, ARAB
EN
Output indication
level, OD
Level
Login timeout
1 - 120 min
10 min
Backlight timeout
0 - 120 min
2 min
Password daily
3 -digit, 0 - 999
100
Password service
3 -digit, 0 - 999
200
Password commission
3 -digit, 0 - 999
300
IO config
System configuration
ICAD+NC, ICAD, AKV/A+NC, AKV/A, NC only
ICAD + NC
Level signal setup
AKS 4100, AKS 41, Current, Voltage
AKS4100
Voltage at low liquid level
0-10V
0 V
Voltage at high liquid level
0-10V
10 V
Current at low liquid level
0-20 mA
4 mA
Current at high liquid level
0-20 mA
20 mA
Valve position setup
Not used, Current, Voltage
Not used
Voltage at closed valve position
0-10V
0 V
Voltage at open valve position
0-10V
10 V
Current at closed valve position
0-20 mA
4 mA
Current at open valve position
0-20 mA
20 mA
Common alarm setup
D04, High alarm, D03, Disp only
High alarm
Multiple valve setup
Not used, 2 same cap, 2 dif cap, 3 same cap, 3 dif cap
Not used
Multiple valve pattern
Parallel,Sequence
Parallel
Valve A capacity
0-100 %
50%
Valve B capacity
0-100 %
50%
Valve C capacity
0-100 %
30%
ICAD takeover OD
0-100%
80%
IO module setup
Used, Not used
Not used
Communication
CAN ID
1 - 127
1
CAN baudrate
20k, 50k, 125k, 250k, 500k, 1M
500k
Modbus ID
0 - 120
1
Modbus baudrate
0, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400
19200
Modbus mode
8N1, 8E1, 8N2
8E1
Modbus mapping
Operation, Setup
Operation
Valve B CAN ID
1 - 127
2
Valve C CAN ID
1 - 127
3
IO Mod. CAN ID
1 - 127
4
To be continued......