User Guide | Liquid level controller, EKE 347
© Danfoss | DCS (ADAP-KOOL®) | 2016-04
DKRCI.PD.RP0.A4.02 | 17
Label
Alarm name
Modbus
PNU
Bit
number
A1
Upper level
1901
8
A2
Lower level
1901
9
A92
Oscillation in level signal
1901
10
A96
Valve position
1901
14
A97
Multiple valve capacity
1901
15
E1
Internal error
1901
0
E21
Level signal out of range
1901
1
E22
Valve position signal out of range
1901
2
E96
AKS 4100 error
1901
3
A45
Standby mode
1901
4
A99
Valve B communication
1901
5
A98
Valve C communication
1901
6
A85
Communication to master lost
1901
7
A91
Valve B alarm
1902
8
I11
Valve B capacity
0
100
50
%
0
3047
YES
YES
I12
Valve C capacity
0
100
33
%
0
3048
YES
YES
I17
ICAD takeover OD
0
100
80
%
0
3052
NO
YES
I19
IO module setup
0
1
0
0
3091
YES
YES
0 = Not used | 1 = Used
G01
CAN ID
1
127
1
0
4032
NO
NO
G02
Can baudrate
0
5
4
0
4033
NO
NO
0 = 20k | 1 = 50k | 2 = 125k | 3 = 250k | 4
= 500k | 5 = 1M
G06
Modbus ID
0
120
1
0
3055
NO
YES
G05
Modbus baudrate
0
8
6
0
3056
NO
YES
0 = 0 | 1 = 1200 | 2 = 2400 | 3 = 4800 |
4 = 9600 | 5 = 14400 | 6 = 19200 | 7 =
28800 | 8 = 38400
G08
Modbus mode
0
2
1
0
3057
NO
YES
0 = 8N1 | 1 = 8E1 | 2 = 8N2
G07
Modbus mapping
0
1
0
0
3058
NO
YES
0 = Operation | 1 = Setup
G09
Valve B CAN ID
1
127
2
0
3088
YES
YES
G10
Valve C CAN ID
1
127
3
0
3089
YES
YES
G11
IO Mod. CAN ID
1
127
4
0
3090
YES
YES
B01
Controller state
0
6
0
0
4001
YES
NO
0 = Powerup | 1 = Stop | 2 = Auto | 3 =
Manual | 4 = Slave | 5 = IO | 6 = Safe
u01
Actual level
0
100
0
%
1
4002
NO
NO
u02
Actual reference
0
100
0
%
1
4003
YES
NO
u24
Actual OD
0
100
0
%
1
4004
NO
NO
u33
Actual valve position
0
100
0
%
1
4005
NO
NO
u10
Digital input status
0
1
0
0
4006
NO
NO
0 = Off | 1 = On
u31
Actual level signal voltage
0
100
0
V
1
4007
NO
NO
u30
Actual level signal current
0
24
0
mA
1
4008
NO
NO
B02
Actual position signal voltage
0
100
0
V
1
4009
NO
NO
u32
Actual position signal current
0
100
0
mA
1
4010
NO
NO
B03
Actual OD A
0
100
0
%
1
4011
NO
NO
B04
Actual OD B
0
100
0
%
1
4012
NO
NO
B05
Actual OD C
0
100
0
%
1
4013
NO
NO
o18
Manual Mode
0
1
0
0
4014
NO
NO
0 = Off | 1 = On
o45
Manual OD
0
100
50
%
1
3059
NO
NO
B08
Manual low alarm
0
1
0
0
3060
NO
NO
0 = Off | 1 = On
B06
Manual high alarm
0
1
0
0
3061
NO
NO
0 = Off | 1 = On
B07
Manual common alarm
0
1
0
0
3062
NO
NO
0 = Off | 1 = On
B09
Apply defaults
0
1
0
0
3063
YES
NO
0 = None | 1 = Factory
B11
Oscillation amplitude
0
100
0
%
1
4028
YES
NO
B10
Oscillation period
0
3600
0
s
0
4029
YES
NO
A90
Valve C alarm
1902
9
A88
Control method conflict
1902
10
A87
Common alarm HW conflict
1902
11
A86
Min/max OD conflict
1902
12
E95
Sensor supply overload
1902
13
E99
DO4 overload
1902
14
E97
Too much current AI3
1902
15
E98
Too much current AI4
1902
0
A89
Multiple valve setup conflict
1902
1
A80
Valve B CAN ID conflict
1902
2
A81
Valve C CAN ID conflict
1902
3
A82
IO module CAN ID conflict
1902
4
A83
IO module communication
1902
5