User Guide | Liquid level controller, EKE 347
© Danfoss | DCS (ADAP-KOOL®) | 2016-04
DKRCI.PD.RP0.A4.02 | 16
Label Parameter name
Min
value
Max
value
Default
Unit
Deci-
mals
Modbus
PNU
Locked
by main
switch
EEPROM Enumeration
r12
Main switch
0
1
0
0
3001
NO
YES
0 = Off | 1 = On
R01
Liquid level setpoint
0
100
50
%
1
3002
NO
YES
N07
Operation Mode
0
2
0
0
3003
YES
YES
0 = Master | 1 = Slave | 2 = IO
a02
Lower level limit
0
100
15
%
0
3004
NO
YES
a01
Upper level limit
0
100
85
%
0
3005
NO
YES
a07
Level alarm mode
0
1
0
0
3006
NO
YES
0 = Time | 1 = Hysteresis
a04
Lower delay
0
999
10
s
0
3007
NO
YES
a03
Upper delay
0
999
50
s
0
3008
NO
YES
a06
Lower level hysteresis
0
20
3
%
1
3009
NO
YES
a05
Upper level hysteresis
0
20
5
%
1
3010
NO
YES
a08
Function common alarm
0
3
0
0
3011
NO
YES
0 = Not follow | 1 = Follow up | 2 = Fol-
low low | 3 = Follow all
a12
Oscillation detect band
0
100
100
%
0
3012
NO
YES
a13
Oscillation detect timeout
2
30
20
min
0
3013
NO
YES
a25
Force pump OFF in stopped mode
0
1
0
0
3117
NO
YES
0 = Off | 1 = On
a14
IO Lower level limit
0
100
5
%
0
3101
NO
YES
a15
IO Upper level limit
0
100
95
%
0
3102
NO
YES
a16
IO Lower level hysteresis
0
20
3
%
1
3103
NO
YES
a17
IO Upper level hysteresis
0
20
3
%
1
3104
NO
YES
a18
IO Lower delay
0
999
10
s
0
3105
NO
YES
a19
IO Upper delay
0
999
50
s
0
3106
NO
YES
a20
IO Level limit
0
100
50
%
0
3107
NO
YES
a21
IO Level delay
0
999
10
s
0
3108
NO
YES
a22
IO Level hysteresis
0
20
3
1
3109
NO
YES
a23
IO Level action
0
1
0
0
3110
NO
YES
0 = Falling | 1 = Rising
N03
Control Method
0
2
2
0
3014
NO
YES
0 = On/off | 1 = P-ctrl | 2 = PI-ctrl
n35
Regulating principle
0
1
0
0
3015
NO
YES
0 = Low | 1 = High
n04
P-band
5
200
30
%
1
3016
NO
YES
n05
Integration time Tn
60
600
400
s
0
3017
NO
YES
n34
Neutral zone
0
25
2
%
1
3018
NO
YES
N06
Difference
0,5
25
2
%
1
3019
NO
YES
n13
Period time for AKV/AKVA
3
15
6
s
1
3020
NO
YES
n33
Minimum OD
0
0
%
0
3021
NO
YES
n32
Maximum OD
1
100
100
%
0
3022
NO
YES
o11
Language
0
0
0
0
3023
YES
YES
0 = $ActiveLanguageList
o17
Output indication
0
1
0
0
3024
NO
YES
0 = Level | 1 = OD
K04
Login timeout
1
120
10
min
0
3025
NO
YES
K06
Backlight timeout
0
120
2
min
0
3026
NO
YES
o05
Password daily
0
999
100
0
3027
NO
YES
K02
Password service
0
999
200
0
3028
NO
YES
K03
Password commission
0
999
300
0
3029
NO
YES
K05
Contrast
0
100
40
%
0
3030
NO
YES
K01
Brightness
0
100
80
%
0
3031
NO
YES
I09
System configuration
0
4
0
0
3032
YES
YES
0 = ICAD+NC | 1 = ICAD | 2 = AKV/A+NC
| 3 = AKV/A | 4 = NC only
o31
Level signal setup
0
3
0
0
3033
YES
YES
0 = AKS4100 | 1 = AKS41 | 2 = Current |
3 = Voltage
o32
Voltage at low liquid level
0
0
V
1
3034
NO
YES
o33
Voltage at high liquid level
10
10
V
1
3035
NO
YES
I06
Current at low liquid level
0
4
mA
1
3036
NO
YES
I07
Current at high liquid level
20
20
mA
1
3037
NO
YES
o34
Valve position setup
0
2
0
0
3038
YES
YES
0 = Not used | 1 = Current | 2 = Voltage
I02
Voltage at closed valve position
0
0
V
1
3039
NO
YES
I03
Voltage at open valve position
10
10
V
1
3040
NO
YES
I04
Current at closed valve position
0
4
mA
1
3041
NO
YES
I05
Current at open valve position
20
20
mA
1
3042
NO
YES
I18
Common alarm setup
0
3
1
0
3043
YES
YES
0 = DO4 | 1 = High Alarm | 2 = DO3 | 3
= Disp only
I08
Multiple valve setup
0
4
0
0
3044
YES
YES
0 = Not used | 1 = 2 same cap | 2 = 2 dif
cap | 3 = 3 same cap | 4 = 3 dif cap
I13
Multiple valve pattern
0
1
0
0
3045
NO
YES
0 = Parallel | 1 = Sequence
I10
Valve A capacity
0
100
50
%
0
3046
YES
YES
Modbus parameters
Software version: 1.62.xx