Setup & service menu - COMMISSIONING
(Continued)
Parameter
Options
Default
values
Service
Controller state
-
Actual level
-
Actual referrence
-
Actual OD
-
Actual valve position
Digital input status
-
Actual level signal voltage
Actual level signal current
-
Actual position signal voltage
Actual position signal current
Actual OD A
Actual OD B
Actual OD C
Manual Mode
On, Off
Off
Manual OD
0 - 100%
50.0%
Manual low alarm
Off-On
Off
Manual high alarm
Off-On
Off
Manual common alarm
Off-On
On
Apply defaults
None, Factory
None
Setup wizard
Setup wizard
Re-run Setup wizard
-
I/O check
Main switch EKE act:
Off
AKS 4100 EKE act:
-
ICAD EKE act:
-
Nor. Close (NC) EKE act:
-
Upper lvl (alarm) EKE act:
-
Lower lvl (alarm) EKE act:
-
Controller name
Controller name
Type in controller name
-
Read & Write
Read only
Alarm and error codes:
When detecting an alarm from external sources or the flashing bell in the display,
the alarm description can be found as a text message in the Status menu under
Active alarms.
Both alarms and errors will be shown here.
If more alarms/errors occur simultaneously, they will be shown as subsequent text
lines.
Alarms:
Upper level
Lower level
Standby mode
Valve B CAN ID conflict
Valve C CAN ID conflict
IO module CAN ID conflict
IO module communication
Communication to master lost
Min/max OD conflict
Common alarm HW conflict
Control method conflict
Multiple valve setup conflict
Valve C alarm
Valve B alarm
Oscillation in level signal
Valve position
Multiple valve capacity
Valve C communication
Valve B communication
Errors:
Internal error
Level signal out of range
Valve position signal out of range
Sensor supply overload
AKS 4100 error
Too much current AI3
Too much current AI4
DO4 overload