User Guide  |  Liquid level controller, EKE 347 

© Danfoss | DCS (ADAP-KOOL®) | 2016-04

DKRCI.PD.RP0.A4.02 | 7

Setup & service menu - COMMISSIONING 

(Continued)

Parameter

Options

Default 

values

Service

Controller state

 -  

Actual level

 -  

Actual referrence

 -  

Actual OD

 -  

Actual valve position

Digital input status

 -  

Actual level signal voltage

Actual level signal current

 -  

Actual position signal voltage

Actual position signal current

Actual OD A

Actual OD B

Actual OD C

Manual Mode

On, Off

Off

Manual OD

0 - 100%

50.0%

Manual low alarm

Off-On

Off

Manual high alarm

Off-On

Off

Manual common alarm

Off-On

On

Apply defaults

None, Factory

None

Setup wizard

Setup wizard

Re-run Setup wizard

 -  

I/O check

Main switch EKE act:

Off

AKS 4100 EKE act:

 -  

ICAD EKE act:

 -  

Nor. Close (NC) EKE act:

 -  

Upper lvl (alarm) EKE act:

 -  

Lower lvl (alarm) EKE act:

 -  

Controller name

Controller name

Type in controller name

 -  

Read & Write
Read only

Alarm and error codes:

When detecting an alarm from external sources or the flashing bell in the display, 

the alarm description can be found as a text message in the Status menu under 

Active alarms.

Both alarms and errors will be shown here.

If more alarms/errors occur simultaneously, they will be shown as subsequent text 

lines.

Alarms:

Upper level
Lower level
Standby mode
Valve B CAN ID conflict
Valve C CAN ID conflict
IO module CAN ID conflict
IO module communication 
Communication to master lost
Min/max OD conflict
Common alarm HW conflict
Control method conflict
Multiple valve setup conflict
Valve C alarm
Valve B alarm
Oscillation in level signal
Valve position
Multiple valve capacity
Valve C communication
Valve B communication

Errors:

Internal error
Level signal out of range
Valve position signal out of range
Sensor supply overload
AKS 4100 error
Too much current AI3
Too much current AI4
DO4 overload

Содержание EKE 347

Страница 1: ...e the liquid flow to or from the reservoir Liquid level control Alarm if the set alarm limits are exceeded Relay outputs for upper and lower level lim its and for alarm level User friendly and easy se...

Страница 2: ...ers to the EKE 347 Operation monitoring and data collection can then be performed via PLC from a SCADA system With the guided micro wave rod AKS 4100 4100U it is possible to set the refrigerant level...

Страница 3: ...unctions in connection with the max permissible level Receiver condenser The control system s short reaction time makes it very suited for high pressure float systems with small refrigerant charges IC...

Страница 4: ...alarm present and Upper level alarm off no alarm present Additional to the external connected alarm audio video sources a Bell symbol will flash in the upper right corner in case of an alarm To see m...

Страница 5: ...wable parameters including password issuing and re run of Setup wizard Service level is for service personnel and has fewer rights than commissioning The lowest level is for Daily use and allows only...

Страница 6: ...0 100 Display Language EN CN PT RU SP FR IT GER ARAB EN Output indication level OD Level Login timeout 1 120 min 10 min Backlight timeout 0 120 min 2 min Password daily 3 digit 0 999 100 Password serv...

Страница 7: ...oller name Controller name Type in controller name Read Write Read only Alarm and error codes When detecting an alarm from external sources or the flashing bell in the display the alarm description ca...

Страница 8: ...ing output Data communication MODBUS RTU Communication to system controller MODBUS on RS485 galvanic isolation 500 V d c CAN Communication to other EKE controllers Supported Modbus Commands Supported...

Страница 9: ...Normally Closed 34 35 circuits The relay will switch according to the programmed setting 25 27 Relay for low level limit Installer can choose between Normally Open 26 27 or Normally Closed 25 26 circu...

Страница 10: ...ay ModBUS 4 20 mA 24 V DC yellow blue orange ICAD 1st gen ICAD ICM feedback ICAD 2nd gen blue 24 V AC L N 1 2 3 yellow gray orange ICAD 1st gen pre 2010 ICAD 2nd gen 2010 yellow green brown brown whit...

Страница 11: ...AC 20 15 VA 24 V DC 20 10 W Common Normally Open or Normally Closed Low Level Alarm Normally Open or Normally Closed High Level Alarm Normally Open or Normally Closed 37 29 28 27 26 25 36 35 34 33 32...

Страница 12: ...F Application Open Close solenoid valve with coil 24 V 230V NO 4 NC 3 C 3 NO 3 NC 2 C 2 NO 2 NO 1 C 1 NC 1 POWER SUPPLY Voltage 24 230 V a c Connection examples AKS 4100 AKS 4100U Danfoss M84H0075_1 A...

Страница 13: ...these options 2 valves with same capacity 2 valves with different capacity 3 valves with same capacity 3 valves with different capacity Multivalve Additionally the master must be programmed in IO conf...

Страница 14: ...0 CAN H CAN L GND 15 16 17 18 Jumper 15 16 Jumper 15 16 D02 D03 D01 NC 2 C 2 NO 2 NC 3 C 3 NO 3 NO 1 C 1 NC 1 When more controllers are connected via CAN bus each end of the bus must be terminated wit...

Страница 15: ...splay s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until the Bios menu appears 2 Select the MCX selection menu Sele...

Страница 16: ...ES 0 Low 1 High n04 P band 5 200 30 1 3016 NO YES n05 Integration time Tn 60 600 400 s 0 3017 NO YES n34 Neutral zone 0 25 2 1 3018 NO YES N06 Difference 0 5 25 2 1 3019 NO YES n13 Period time for AKV...

Страница 17: ...tate 0 6 0 0 4001 YES NO 0 Powerup 1 Stop 2 Auto 3 Manual 4 Slave 5 IO 6 Safe u01 Actual level 0 100 0 1 4002 NO NO u02 Actual reference 0 100 0 1 4003 YES NO u24 Actual OD 0 100 0 1 4004 NO NO u33 Ac...

Страница 18: ...material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being...

Отзывы: