e
32f
Service parameter(s) 22-24
22 Pump exercise
Circuit
Setting range
Factory setting
I
ON / OFF
ON
Exercises the pump to avoid blocking in periods without heat
demand.
ON:
The pump is switched ON for 1 minute every
third day around noon.
OFF:
The pump exercise is not active.
23 Valve exercise
Circuit
Setting range
Factory setting
I
ON / OFF
OFF
Exercises the valve to avoid blocking in periods without heat
demand.
ON:
The valve receives a signal to open and
close every third day around noon.
OFF:
The valve exercise is not active.
24 Gear motor / thermo actuator
Circuit
Setting range
Factory setting
I
ON / OFF
ON
Choose the actuator type for your valve.
ON:
Gear motor
OFF:
Thermo actuator (ABV type)
Control parameters (lines 4-7) are overruled if thermo actuator is
chosen (OFF).