ECL Card settings
(circuit II)
30b
A
Time and date
Section 17
B
System information
Sections 18 & 19
C
Setting ranges
Factory settings
Your settings
1
2
3
4
Proportional band, Xp
1 ... 250 K
80 K
See section 26
5
Integration time constant, Tn
5 ... 999 sec.
20 sec.
See section 26
6
Running time of the motorized control
valve
5 ... 250 sec.
15 sec.
See section 26
7
Neutral zone, Nz
0 ... 9 K
3 K
See section 26