e
Service parameter(s) 110-129
126-129 Dates for heating OFF period
The heating OFF period is active in the modes 'scheduled
operation', 'constant comfort temperature' and 'constant
setback temperature'. The factory settings ensure that the
heating is stopped between April 15 and October 15.
Factory settings:
Start heating OFF period: April 15
Stop heating OFF period: October 15
Month,
setting range
Day,
setting range
2
February
1 - 30
3
March
1 - 30
4
April
1 - 30
5
May
1 - 30
6
June
1 - 30
7
July
1 - 30
8
August
1 - 30
9
September
1 - 30
10
October
1 - 30
11
November
1 - 30
12
December
1 - 30
13
14
15
Line 126: Date (1 ... 30)
Line 128: Date (1 ... 30)
Line 127: Month (2 ... 12)
Line 129: Month (2 ... 12)
Heating ON
Heating ON
Heating OFF
Time
Start date
Stop date
110 ... 117 Heat meter parameters
Circuit
Setting range
Factory setting
I / II
These settings are only used when a heat meter signal is applied
to the ECL Comfort controller (see the documentation for the
used module).
The lines are visible if an M-Bus module (ECA 84 or ECA 73) is
connected to the ECL Comfort 300.