![Danfoss EC-C1200-450 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/danfoss/ec-c1200-450/ec-c1200-450_user-manual_3449260014.webp)
If the control cabling is installed close with the power cabling, make sure that minimum separation distance is 100 mm
and crossings are at 90 degrees. Make sure that all terminal connections are tightened correctly by the instructions.
Electric device must not be opened (excluding the connection box lid). Any attempt causes loss of warranty.
Within the European Union, all machinery in which this product is used must comply with Directive 98/37/EC, Safety of
Machinery. In particular, the machine manufacturer is responsible for providing a main switch and ensuring the electrical
equipment complies with EN60204-1.
Use correct personal protective equipment when you are near the electric device.
Read the instructions in this user guide before you start to install the electric device.
Operation safety
Do not use the electric device without correctly dimensioned and operating cooling system.
Maximum operation temperature must not be exceeded to avoid permanent damage to the electrical device.
The requirements of this user guide and other related instructions and standards must be followed
Make sure that the cooling system is in use when the DC-link is powered.