Caution
Check installed fuses before making any settings.
Power
steps
Heating power in kW
Control panel (single phase 1-N) fuse size
(A)
Control panel (three phase 3-N) fuse size (A)
1
3, immersion heater only
16
10
2
6, immersion heater only
30
16
3
9, immersion heater only
40
16
4
12, immersion heater only
—
20
5
15, immersion heater only
—
25
+4
12, immersion com-
pressor
—
25
+5
15, immersion com-
pressor
—
25
230V 1-N Electric auxiliary heater
The following settings are made in the Service Menu. If not already in the Service Menu, enter the Service Menu by pressing and holding
left (<) arrow for at least 5 seconds. Use
+
or
–
to move up and down in the menu.
!
Electric auxiliary heater for 230V, 1-N. Step 3 is highest setting
Setting of electric auxiliary heater for 230V, 1-N. Max step 3 in the SERVICE menu:
!
SERVICE
!
AUX. HEATER.
!
MAX STEP
!
Select max step
400V 3-N Electric auxiliary heater
The following settings are made in the Service Menu. If not already in the Service Menu, enter the Service Menu by pressing and holding
left (<) arrow for at least 5 seconds. Use
+
or
–
to move up and down in the menu.
!
Electric auxiliary heater for 400V, 3-N. Step 5 is highest setting
5 is highest setting
Setting of electric auxiliary heater for 400V, 3-N. Max step 5 in the SERVICE menu:
!
SERVICE
!
AUX. HEATER.
!
MAX STEP
!
Select max step