Parameter
Meaning
COMPR.HE
0 = compressor heater off
1 = compressor heater on
DRIP TRAY
0 = drip tray heater off
1 = drip tray heater on
REV.V. HOT WATER
0 = reversing valve in heating mode
1 = reversing valve in hot water mode
IMM. HEAT 1
0 = stop of internal immersion heater power stage 1
1 = start of internal immersion heater power stage 1
IMM. HEAT 2
0 = stop of internal immersion heater power stage 2
1 = start of internal immersion heater power stage 2
IMM. HEAT 3
0 = stop of internal immersion heater power stage 3
1 = start of internal immersion heater power stage 3
EXT.AUX.HEATER
0 = stop external heat source (230V)
1 = start external heat source (230V)
POT.FREE
0 = potential free output for control of auxiliary heater open
1 = potential free output for control of auxiliary heater closed
CIRC. PUMP DC 1
0 = stop circulation pump in discharge circuit 1
1 = start circulation pump in discharge circuit 1
SHUNT DC 1
–
= closes shunt in discharge circuit 1
0 = shunt unaffected
+
= opens shunt in discharge circuit 1
CIRC. PUMP DC 2
0 = stop circulation pump in discharge circuit 2
1 = start circulation pump in discharge circuit 2
SHUNT DC 2
– = closes shunt in discharge circuit 2
0 = shunt unaffected
+ = opens shunt in discharge circuit 2
SYSTEM SHUNT
– = closes shunt
0 = shunt unaffected
+ = opens shunt
RET.L. HP SHUNT
– = closes return line shunt in systems with buffer tank
0 = shunt unaffected
+ = opens shunt in systems with buffer tank
REV. V. POOL
0 = reversing valve in normal mode
1 = reversing valve in pool mode
ALARM
0 = no voltage on output 201.6 External alarm
1 = 230V on output 201.6 External alarm
DIGITAL OUT 5V
0 = no voltage on output 204.1
1 = 5V (2mA) on output 204.1
5.2
Test the circulation pump
Optimum (variable speed) circulation pump
!
If a fixed speed circulation pump is used, may be the case for DHP-AQ Mini, do the test according to the next
chapter: "
Constant speed circulation pump
"
Optimum (variable speed) circulation pump is factory installed in DHP-AQ Midi and DHP-AQ Maxi. The OPTIMUM option is however not
activated from factory.
The following settings are made in the MANUAL TEST menu. To activate MANUAL TEST, see description above. Use
+
or
–
to move up
and down in the menu.
Commissioning
VIGFH102
Danfoss Heating Solutions
16