To activate shunt group 1 the value of SHUNT GROUP 1 must either be set to HEAT CURVE or to CONSTANT TEMP.
Activated in SERVICE -> INSTALLATION ->SYSTEM.
•
When HEAT CURVE is selected, the shunt group controls to the set heat curve.
•
When CONSTANT TEMP is selected, shunt group controls a constant temperature regardless of outdoor tem-
perature. Enter the constant temperature for SHUNT GROUP 1 by giving the temperature for CONSTANT TEMP
in INFORMATION -> SHUNT GROUP 1.
•
When cooling the value of WHEN COOLING is set to AUTO or OPEN. Activated in INFORMATION -> SHUNT
GROUP 1.
To activate hot water production, set the HOT WATER value to ON. Activated in INFORMATION -> HOT WATER. The
start value for hot water production is factory set to 40°C. The value of START can be changed in SERVICE -> HOT
WATER.
11.4
Manual test
Caution! The installation may only be commissioned if the heating system and water heater have been
filled and bled. Otherwise the circulation pump can be damaged.
Caution! Any alarms that may occur in connection with the installation must be fault-traced.
Test operate and at the same time check the function of the components. If necessary remove the lower front
hatch, see instruction below
11.4.1
Remove the lower front hatch
1.
Unscrew the screws and washers in the lower edge of the front hatch.
2.
Pull the front hatch down so that the front hatch is released from the two catches.
Installation instructions VMGFD102 – 67