Parameter
Meaning
DISTRIBUTION CIRCUIT 1 - 2 Activates the shunt group function and indicates if the shunt group is to be controlled by the
heat curve or by a constant temperature.
Factory setting:
, range:
– HEAT CURVE – CONSTANT TEMP
SHUNT TIME - Indicates the shortest permitted interval between control signals to the shunt.
Factory setting: 60S, range: 10S – 99S
BUFFER TANK
Activates the buffer tank function.
Factory setting:
, range:
– ON
OPTIMUM
Activates the Optimum function, makes use of a speed controlled circulation pump possible.
Factory setting:
, range:
– ON
CURRENT LIMITER
Activates the current limiting function. An expansion card must be installed for current meas-
urement.
Factory setting:
, range:
– ON
START UP CHECK
Activation of the function for checking temperature and pressure at compressor start.
If deviations are found this is indicated by an alarm.
Factory setting: ON, range:
– ON
SERVICE TIME
Note! Only used for test operation. The heat pump counts 60 times as fast,
which means that the waiting times are eliminated during test operation.
0 = deactivates SERVICE TIME
1 = activates SERVICE TIME, which speeds up the control system’s integral calculation and start
delay by 60 times.
Factory setting: 0, range 0 – 1
FACTORY SET
Indicates if resetting to factory settings must be done.
CANCEL: Starting point, no changes made.
RADIATOR: Reset factory settings for radiator system
FLOOR: Reset factory settings for underfloor heating.
RESET OPER. TIME
Used to reset operating times.
0 = no reset of operating times
1 = reset of operating times to zero
Factory setting: 0, range 0 – 1