Parameter
Meaning
SENSOR CALIBRATION
OUTD
SYSTEM SUPPLY
SUPPLY LINE
RETURN LINE
HOT WATER
HOT WATER TOP
REFR 1
REFR 2
DISCH. PIPE
DEFR SENSOR
BUFFER TANK
DISTRIBUTION CIRCUIT 1
DISTRIBUTION CIRCUIT 2
POOL
SUCTION GAS
Factory setting: 0, range: -5°C – 5°C
EXTERNAL FACTOR: Affects sensors that are installed inside the heat pump.
Factory setting: 0, range: 0°C – 20°C
VERSION
Indicates the version number of the software in the control.
DISPLAY
HUB
HP (heat pump card)
EXP (expansion card)
EXV (expansion valve card)
LOG TIME
Time interval between collection points of temperature history in minutes. The history graphs
always show the 60 last collection points, which means that the graphs can display history
from 1 hour up to 60 hours ago.
(The function is not active if there is an active alarm).
Factory setting: 1M, range: 1M – 60M
10.8
DEFROST
Parameter
Meaning
DEFR OFFSET
Adjusting the defrost curve. Negative value moves the defrost curve down which means
that it takes a longer time before defrosting starts. Positive value moves the defrost curve
up which means that it takes a shorter time before defrosting starts.
Factory setting: 0°C, range: -20°C – 20°C
STOP DEFR
The temperature that refrigerant sensor 2 must reach to complete a defrost.
Factory setting: 38°C, range: 7°C – 60°C
60 – Installation instructions VMGFD102