Installation and User Guide
DEVIreg™ Multi
FEC | Produced by Danfoss ©
43
Z11
Channel #6 > Sensor type
T17
#6 Sensor type
0
7
1 – PT1000
Enum 9
RW
3113
Z12
Channel #6 > Relay Status RO/RC
T18
#6 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
0
1
0 – RC
Enum 10
RW
3114
Z13
Channel #6 > Relay Test 5/30 sec .
T19
#6 Relay Test 5/30 - Every 5 sec . switching for 30 sec .
0
1
0 – STOP
Enum 6
RW
3115
X1
Channel #7 > Regulation Type
V1
#7 Regulation Type: 1S – Single Sensor,
PR – Power Regulation
0
1
1 – 1S
Enum 1
RW
3116
X2
Channel #7 > Temp & Hysteresis
V2
#7 Set Temperature
-50
200
5
°C
RW
3117
V3
#7 Set +-Hysteresis
0 .2
6
0 .4
°C
RW
3118
X3
Channel #7 > On Time & Period
V4
#7 Set On Time
1
0
15
min .
RW
3119
V5
#7 Set PR Period (max . 900 minutes)
0
900
30
min .
RW
3120
X4
Channel #7 > Alarm Temps & En/Dis
V6
#7 Alarm Temp En/Dis
0
1
0 – Dis
Enum 5
RW
3121
V7
#7 Alarm min . Temp
-50
0
0
°C
RW
3122
V8
#7 Alarm max . Temp
0
200
60
°C
RW
3123
X5
Channel #7 > CableOK?
V9
#7 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
0
1
0 – Dis
Enum 5
RW
3124
V10
#7 CableOK? = NO/NC . Set up DI7 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
0
1
1 – NO
Enum 8
RW
3125
X75
Power calculator > Channel Power #7
V11
#7 Channel Power (max . 32000)
0
32000
0
W
RW
3126
X8
Channel #7 > Manually On/Of
V12
#7 Manually On/Of Time – Set up period of time
for MOn or MOf status (max . 900 minutes)
1
900
1
min .
RW
3127
V13
#7 Status On or Of for mode Heating Manually
0
1
0 – Of
Enum 11
RW
3128
V14
#7 Manually On/Of Start or Stop control mode .
Caution: this mode may cause overheating and
damage!
0
1
0 – STOP
Enum 6
RW
3129
X9
Channel #7 > Channel ON/OFF
V15
#7 Channel ON/OFF If OFF symbol # on the
main screen, algorithm is stopped, but real
Temp . is shown
0
1
0 – OFF
Enum 7
RW
3130
X11
Channel #7 > Sensor type
V17
#7 Sensor type
0
7
1 – PT1000
Enum 9
RW
3131
X12
Channel #7 > Relay Status RO/RC
V18
#7 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
0
1
0 – RC
Enum 10
RW
3132
X13
Channel #7 > Relay Test 5/30 sec .
V19
#7 Relay Test 5/30 - Every 5 sec . switching for 30 sec .
0
1
0 – STOP
Enum 6
RW
3133