© Danfoss | 2019.02 | 9
VI.GM.A2.02
CCR3+ Controller
ENGLISH
READINGS MENU:
No. Name
Description
1
O1..O4
Output status (Defined output O1..O4)
Open
- no alarm or break alarm circuit
Closed
– shortcut to ground in alarm circuit
See Outputs settings in Installer Menu.
2
B1..B3
Input status
Open
- input Bx open
Closed
– input B1 close to G
Free contact relay (not used in CCR3+ process, only for monitoring in BMS). Binary inputs or PT1000
sensor (5V, 1mA).
3
RT Clock
The Real Time clock, show current time, date, day of the week.
Data used in archive file.
4
S0-main temp.
S0 – value of (°C) supply temperature. The same readings apply to sensors S1 … S20.
Open
- no sensor or break sensor circuit
Closed
– shortcut to ground in sensor circuit
Fault
– temp. values exeed Fault temp. max or is bellow Fault temp. max (correspondent to Fault temp.
settings in Installer Menu)
5
Ret.Set.Temp
Information about setting return temperature correspondent to current flow temperature, in °C degree.
Required range set in points in the Installer Menu. Function used for temperature alarm output.
Set. Temperature is = Return Set. Tempe/- Shift T. Set.
6
Alerts
General information about CCR3+ status
OK
– system is running without alarms
Alert (red)
– system has alarms
Riser Status (sensors: S1-S36; valves: V1-V36)
7
Riser
Number of risers (look to: Advanced Menu)
Riser statuses are indicated with color.
OK
– riser status is OK
High (red)
- if temp. on Sx sensor is higher then Ret.Set.Temp
Low (blue)
- if temp. on Sx sensor is lower then Ret.Set.Temp.
Open (yellow)
- no sensor or break sensor circuit
Closed (grey)
- shortcut to ground in sensor circuit
N/A (white)
- non relevant (non selected) risers
8
Valve output
Status of valve: V1 … V36
1
– open, valve output closed to C (powered up), (taking PWM into account).
0
– valve closed, valve output closed to C (powered down), (taking PWM into account).
Valve is 1-Open if: PWM min < Valve % <PWM max
9
Valve [%]
… ..% – valve open ratio – percentage of filling the PWM function (0 … 100 % in 10 % steps)
10
Temperature
[°C]
Temperature readings in riser
Open
- no sensor or break sensor circuit
Closed
– shortcut to ground in sensor circuit
11
Set. Temp.[°C]
Information about return temperature correspondent to Ret.Set.Temp and Shift setting (correspondent
to Shift T.Set in Shifting Menu)
Set. Temperature is = Return Set.
Tempe/- Shift T. Set.
12
Alerts
Temperatures status (same color as described in pos. “Riser status”):
Riser RX – riser status information:
OK
– riser status is OK
High (red)
- if temp. on Sx sensor is higher then Ret.Set.Temp
Low (blue)
- if temp. on Sx sensor is lower then Ret.Set.Temp.
Open (yellow)
- no sensor or break sensor circuit
Closed (grey)
- shortcut to ground in sensor circuit
N/A (white)
- non relevant (non configurated) risers
INSTALLER MENU:
No. Name
Description
13
TRet(35)
Required return temperature for measure supply temperature: 35°C
Factory setting: 30°C
14
TRet(40)
Required return temperature for measure supply temperature: 40°C
Factory setting: 35°C
15
TRet(45)
Required return temperature for measure supply temperature: 45°C
Factory setting: 38°C
16
TRet(50)
Required return temperature for measure supply temperature: 50°C
Factory setting: 40°C
17
TRet(55)
Required return temperature for measure supply temperature: 55°C
Factory setting: 42°C
18
TRet(63)
Required return temperature for measure supply temperature: 63°C
Factory setting: 45°C
19
TRet(70)
Required return temperature for measure supply temperature: 70°C
Factory setting: 48°C
20
TRet(80)
Required return temperature for measure supply temperature: 80°C
Factory setting: 54°C
11. CCR3+ DASHBOARD
(Web App Screen)
(continuous)
Содержание CCR3+
Страница 1: ...Danfoss 2019 02 VI GM A2 02 1 ENGLISH CCR3 Controller www danfoss com CCR3 Controller Operating Guide...
Страница 14: ...14 Danfoss 2019 02 VI GM A2 02 CCR3 Controller...
Страница 15: ...Danfoss 2019 02 15 VI GM A2 02 CCR3 Controller...
Страница 16: ...VI GM A2 02 16 Danfoss DHS SRMT SI 2019 02 CCR3 Controller...