CCR3+ Controller

LANGUAGE

No. Name

Description

21

TRet(90)

Required return temperature for measure supply temperature: 90°C

Factory setting: 58°C

22

Integration time

Integration time of the control signal (depend of actuators type). The shorter time, quicker 
temperature changes (no stable regulation). The longer time slower reaction for temperature 
change (stable regulation).

Factory setting: 6 sec

 (for dedicated TWA-Z (NO) actuators); setting range 1-100

23

Proportional factor

Control gain of control signal (depend on actuators type). The higher gain control the bigger 
valves reaction (no stable regulation). The lower gain control weak reaction for temperature 
change (stable regulation).

Factory setting: 50 

(for dedicated TWA-Z (NO) actuators); setting range 1-100

24

Dif. Time

Differential time of control signal. The longer the value, faster control in reaction to the control 
value change - approaching to the set value but not reaching it yet. Too high value results in 
unstable control.

Factory setting: 15

25

PWM interval

Time period of pulse width modulation (PWM}.

Factory setting: 10s

26

PWM min.

At »close« signal to actuator, PWM describes minimum % of open period to the actuator. Lower 
the value, longer the reaction time of the actuator. Too high value can result in not closed valve.

Factory setting: 10%

27

PWM max.

At »open« signal to actuator, PWM describes maximum % of open period to the actuator. Higher 
the value, longer the reaction time of the actuator. Too low value can result in not opened valve.

Factory setting: 90%

28

Fault temp min.

Set lower temperature. Temperature alarm output indicated signal when temperature drop 
below this value.
Setting range between 0 °C and 50 °C

Factory setting: 0 °C

29

Risers Nr

Number of active risers.

Factory setting: 20

30

Current time

Set the real time »Clock, hour & minutes”
e.g.: 12:40

31

Current date

Sets the real date 
e.g.: 2018-02-26

32

Alarm Delay

Alarm delay time (relevant for Output which: Over temperature or Broken Sensor).
Higher the value, longer the reaction time alarm signal.

Factory setting: 0 min

33

Alarm diff.temp.+/-

Set upper/lower deviation temperature counted from Required Return Temperature. 
Temperature alarm output indicated signal when temperature exceed this range.

Factory setting: 5°C

34

Alarm Relay Type

Alarm output

StillOn 

– continuous alarm signal: O4 (24 VDC)

Pulse 

– pulse alarm signal 24 VDC every second

Factory setting: Pulse

35

Archive Frequency

Data archiving interval. The time can be set to any value between 10 seconds and 4 hours. 

Factory setting: 1 min

36

Output O1

Alert Broken Sensor

 (default): O1 output is closed to common (C) when sensor is broken (sensor 

is short-cuted or not connected)

37

Output O2

Alert Low Temp

 (default): O2 output is closed to common (C) when sensor temperature is 

bellow Set. Temperature

38

Output O3

Alert High Temp

 (default): O3 output is closed to common (C) when sensor temperature is 

higher than Set. Temperature

39

Output O4

N/A

: Selected Output O4 not in use

40

Pump protection

Factory setting: YES

41

Summer mode

Enabled 

– Summer mode is switch on (valves are closed, Vx output closed to common (C)

Disabled 

– Summer mode is switch off (valves are operating in normal PWM auto mode)

Factor setting: Enabled

42

Set Settings

Click »Set Settings« to confirm changes.

43

Load settings 1

Load settings from memory 1.

44

Load settings 2

Load settings from memory 2.

45

Save settings 1

Save settings into memory 1.

46

Save settings 2

Save settings from memory 2.

SHIFTING MENU:

No. Name

Description

47

Shift T.Set 1 - 
Shift T.Set 36

Shift return temperature valid for all setting points. It can be adjusted up and down. The lowest 
shift setting is to 10 degrees (anti frost setting value).
Each riser can be adjusted individually, riser by riser (from 1 to 36).

Factory setting: 0±°C

; in range of ±10 °C

Set Settings

Click »Set Settings« to confirm changes.

Load settings 1

Load settings from memory 1.

Load settings 2

Load settings from memory 2.

Save settings 1

Save settings into memory 1.

Save settings 2

Save settings from memory 2.

11.  CCR3+ DASHBOARD 
(Web App Screen) 

(continuous)

ENGLISH

Содержание CCR3+

Страница 1: ...Danfoss 2019 02 VI GM A2 02 1 ENGLISH CCR3 Controller www danfoss com CCR3 Controller Operating Guide...

Страница 2: ...2 Danfoss 2019 02 VI GM A2 02 CCR3 Controller Fig 1 Installation with CCR3 Controller up to 20 risers loops Fig 2 Installation with CCR23 Controller Master and CCR Slave Unit more that 20 risers...

Страница 3: ...bus RS 485 C O1 O4 C common port dedicated to outputs O1 O4 O1 output Alert Broken Sensor O2 output Alert Low Temp O3 output Alert High Temp O4 output not in use C V1 4 C common port dedicated to actu...

Страница 4: ...efined output O2 Defined output O3 Defined output O4 Risers temperature sensors S1 S20 Type of sensor PT1000 B1 Def input B1 B2 Def input B2 B3 Def input B3 CCR3 Master Wiring diagram S0 main sensor P...

Страница 5: ...it Connector port Description 0V 24VDC 0V ground power supply 24 VDC power supply C V21 24 C common port dedicated to actuators V21 V24 outputs to actuators C V24 28 C common port dedicated to actuato...

Страница 6: ...e 30 C Transport temperature 10 60 C IP rating IP 20 Power supply 24 VDC Power consumption Controller only 1 10 VA Power consumption Slave Unit only 1 3 VA Weight 0 3 kg Installation DIN rail 35 mm 1...

Страница 7: ...connected to the controllers input and output connectors 1 Set all parameters on the controller 2 Make sure that there is no external voltage on the temperature sensor plugs 3 Make sure that the volta...

Страница 8: ...password admin1234 Important Change of password to secure any unauthorized interaction from 3rd parties Note You can Skip login for access to data only in CCR3 reading overview only When the setup and...

Страница 9: ...6 1 open valve output closed to C powered up taking PWM into account 0 valve closed valve output closed to C powered down taking PWM into account Valve is 1 Open if PWM min Valve PWM max 9 Valve valve...

Страница 10: ...for Output which Over temperature or Broken Sensor Higher the value longer the reaction time alarm signal Factory setting 0 min 33 Alarm diff temp Set upper lower deviation temperature counted from R...

Страница 11: ...ed Factory setting Odd 57 Modbus address Unit Address for Mobus RTU RS485 Factory setting 1 58 LAN IP address The IP address that the router assigned to this device when it joined the network This num...

Страница 12: ...s reset to admin00X where x is the number of BT blue LED blinks Reset the setting only Go to firmware menu and click on Return Defaults Reset password only but not change other parameters Go to firmwa...

Страница 13: ...sed B4 open closed RTC year RTC month RTC day RTC hour RTC minute B1 open closed B2 open closed B3 open closed S0 temp Ret Set Temp Status alert from 300 to 331 300 301 302 303 304 305 306 307 308 309...

Страница 14: ...14 Danfoss 2019 02 VI GM A2 02 CCR3 Controller...

Страница 15: ...Danfoss 2019 02 15 VI GM A2 02 CCR3 Controller...

Страница 16: ...VI GM A2 02 16 Danfoss DHS SRMT SI 2019 02 CCR3 Controller...

Отзывы: