CCR3+ Controller

ENGLISH

13.  Modbus settings

Supported functions:

1.   Read holding registers (0x03)

2.  Write single register (0x06)

3.  Write multiple registers (0x16)

1. Read holding register start addresses:
 

from 0 to 195:

 

0

 – Valve output riser

(1=output closed - valve is open, 0=output open, valve 
is closed)

 

1

 – Valve output pwm riser

(valve open in percentage: 0% .. 100%, unsigned decimal)

 

2

 – Temperature value

(valve open in percentage: 0% .. 100%, unsigned decimal)

 

3

 – Set temperature

(temperature in °C with one decimal place precision, 
unsigned decimal --> example: 529 = 52.9°C)

 

4

 – Status(alert)*

- 0 

- OK 

- 1

 - temp too low/high

- 4

 - sensor closed (short circuit) 

- 5

 - sensor open (sensor not connected etc...)

Example: To get riser 6 temperature

Formula: (6(Riser) - 1) × 5 + 

2

 (Temp Value) = 27

2. Write single register – data can be written into start addresses:
 

 from 300 to 331

 

- from 400 to 435

3. Write multiple register – data can be written into start addresses:
 

- from 300 to 331

 

- from 400 to 435

180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195

Output 1 open/closed
Output 2 open/closed
Output 3 open/closed
Output 4 open/closed
B4 open/closed
RTC year
RTC month
RTC day
RTC hour
RTC minute
B1 open/closed
B2 open/closed
B3 open/closed
S0 temp
Ret. Set. Temp
Status (alert)

from 300 to 331:

300
301
302
303
304
305
306
307
308
309

310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331

Tret 1
Tret 2
Tret 3
Tret 4
Tret 5
Tret 6
Tret 7
Tret 8
Tret 9
Integration time
Prop factor
Dif. time
PWM interval
PWM min
Pwm max
Riser number
RTC year
RTC month
RTC day
RTC hour
RTC minute
Alarm delay
Alarm diftemp
Alarm type
Valve type
Valve characteristic
Out1
Out2
Out3
Out4
Pump protection
Summer mode

from 400 to 435 :

400
401
402
403
404
405
406
407
408
409

410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429

430
431
432
433
434
435

Shift value 1
Shift value 2
Shift value 3
Shift value 4
Shift value 5
Shift value 6
Shift value 7
Shift value 8
Shift value 9
Shift value 10
Shift value 11
Shift value 12
Shift value 13
Shift value 14
Shift value 15
Shift value 16
Shift value 17
Shift value 18
Shift value 19
Shift value 20
Shift value 21
Shift value 22
Shift value 23
Shift value 24
Shift value 25
Shift value 26
Shift value 27
Shift value 28
Shift value 29
Shift value 30
Shift value 31
Shift value 32
Shift value 33
Shift value 34
Shift value 35
Shift value 36

Содержание CCR3+

Страница 1: ...Danfoss 2019 02 VI GM A2 02 1 ENGLISH CCR3 Controller www danfoss com CCR3 Controller Operating Guide...

Страница 2: ...2 Danfoss 2019 02 VI GM A2 02 CCR3 Controller Fig 1 Installation with CCR3 Controller up to 20 risers loops Fig 2 Installation with CCR23 Controller Master and CCR Slave Unit more that 20 risers...

Страница 3: ...bus RS 485 C O1 O4 C common port dedicated to outputs O1 O4 O1 output Alert Broken Sensor O2 output Alert Low Temp O3 output Alert High Temp O4 output not in use C V1 4 C common port dedicated to actu...

Страница 4: ...efined output O2 Defined output O3 Defined output O4 Risers temperature sensors S1 S20 Type of sensor PT1000 B1 Def input B1 B2 Def input B2 B3 Def input B3 CCR3 Master Wiring diagram S0 main sensor P...

Страница 5: ...it Connector port Description 0V 24VDC 0V ground power supply 24 VDC power supply C V21 24 C common port dedicated to actuators V21 V24 outputs to actuators C V24 28 C common port dedicated to actuato...

Страница 6: ...e 30 C Transport temperature 10 60 C IP rating IP 20 Power supply 24 VDC Power consumption Controller only 1 10 VA Power consumption Slave Unit only 1 3 VA Weight 0 3 kg Installation DIN rail 35 mm 1...

Страница 7: ...connected to the controllers input and output connectors 1 Set all parameters on the controller 2 Make sure that there is no external voltage on the temperature sensor plugs 3 Make sure that the volta...

Страница 8: ...password admin1234 Important Change of password to secure any unauthorized interaction from 3rd parties Note You can Skip login for access to data only in CCR3 reading overview only When the setup and...

Страница 9: ...6 1 open valve output closed to C powered up taking PWM into account 0 valve closed valve output closed to C powered down taking PWM into account Valve is 1 Open if PWM min Valve PWM max 9 Valve valve...

Страница 10: ...for Output which Over temperature or Broken Sensor Higher the value longer the reaction time alarm signal Factory setting 0 min 33 Alarm diff temp Set upper lower deviation temperature counted from R...

Страница 11: ...ed Factory setting Odd 57 Modbus address Unit Address for Mobus RTU RS485 Factory setting 1 58 LAN IP address The IP address that the router assigned to this device when it joined the network This num...

Страница 12: ...s reset to admin00X where x is the number of BT blue LED blinks Reset the setting only Go to firmware menu and click on Return Defaults Reset password only but not change other parameters Go to firmwa...

Страница 13: ...sed B4 open closed RTC year RTC month RTC day RTC hour RTC minute B1 open closed B2 open closed B3 open closed S0 temp Ret Set Temp Status alert from 300 to 331 300 301 302 303 304 305 306 307 308 309...

Страница 14: ...14 Danfoss 2019 02 VI GM A2 02 CCR3 Controller...

Страница 15: ...Danfoss 2019 02 15 VI GM A2 02 CCR3 Controller...

Страница 16: ...VI GM A2 02 16 Danfoss DHS SRMT SI 2019 02 CCR3 Controller...

Отзывы: