Danfoss CCR3+ Скачать руководство пользователя страница 12

12 | © Danfoss | 2019.02

VI.GM.A2.02 

CCR3+ Controller

ENGLISH

FIRMWARE MENU:

Name

Description

Upgrade of firmware

To update CCR3+ with new firmware first download firmware file from Danfoss website. 
Then follow procedure: Browse file -> Start upgrade! 

Reset settings to default

To return all setting to default (except Network settings) click on “Return Defaults” 

Reset to defaults passwords

To reset all passwords to defaults (admin1234) click on “Reset Passwords«.

Reset network settings

Reset all network settings to defaults

NOTE:

 When uploading firmware, do not interrupt the web browser by closing the window, clicking a link, or loading a new page. No 

not power-off CCR3+. It could corrupt the firmware.

When the upload is complete, CCR+ restarts. The upgrade process typically takes several minutes.

LOGIN MENU – push user to change password

No. Name

Description

69

Login

Access with login password enable changes in all setting

Skip login

Access without password allows only data readings. Changes of settings values can not be done.  

11.  CCR3+ DASHBOARD 
(Web App Screen) 

(continuous)

12. SERVICES

Reset Wi-Fi password

Available via long press on reset button (located on LAN port) for at least 5 seconds.
Wi-Fi password is reset to “admin00X” where x is the number of BT (blue) LED blinks.

Reset the setting only

Go to firmware menu and click on “Return Defaults”

Reset password only (but not 
change other parameters)

Go to firmware menu and click on “Reset passwords”

Recovery (device can be 
recover back to factory 
firmware)

Via long press on reset button, power down and with access code “

369

” (code for recovery to 

default firmware). To perform a recovery, you need to make these steps:

1.  turn off power supply
2.  press hardware button
3.  turn on power supply, power led will be ON 
4.  hold button for more than 5 sec until ALL 3 leds turned ON
5.  when all 3 leds is turned immediately release the button

From this moment you need to enter 3 digits code
In this mode there are two hardware button function: 

- short press increase code number,
- long press switch to next code digit

Currently code number is signaled by lighting of led diode: blue led = 1 digit, white led = 2 digit, 
orange led = 3 digit

Example to enter code 123:

- first led diode (blue) is turned ON, then make a short button press 1 time, blue led should 

blink once

- make a long press until white led is turned on
- using short button press 2 times, white led should blinks 2 times
- make a long press until orange led is turned on
- using short button press 3 times, orange led should blinks 3 times
- if code is entered properly than recovery has started. 

DO NOT TURN OFF POWER SUPPLY!

Содержание CCR3+

Страница 1: ...Danfoss 2019 02 VI GM A2 02 1 ENGLISH CCR3 Controller www danfoss com CCR3 Controller Operating Guide...

Страница 2: ...2 Danfoss 2019 02 VI GM A2 02 CCR3 Controller Fig 1 Installation with CCR3 Controller up to 20 risers loops Fig 2 Installation with CCR23 Controller Master and CCR Slave Unit more that 20 risers...

Страница 3: ...bus RS 485 C O1 O4 C common port dedicated to outputs O1 O4 O1 output Alert Broken Sensor O2 output Alert Low Temp O3 output Alert High Temp O4 output not in use C V1 4 C common port dedicated to actu...

Страница 4: ...efined output O2 Defined output O3 Defined output O4 Risers temperature sensors S1 S20 Type of sensor PT1000 B1 Def input B1 B2 Def input B2 B3 Def input B3 CCR3 Master Wiring diagram S0 main sensor P...

Страница 5: ...it Connector port Description 0V 24VDC 0V ground power supply 24 VDC power supply C V21 24 C common port dedicated to actuators V21 V24 outputs to actuators C V24 28 C common port dedicated to actuato...

Страница 6: ...e 30 C Transport temperature 10 60 C IP rating IP 20 Power supply 24 VDC Power consumption Controller only 1 10 VA Power consumption Slave Unit only 1 3 VA Weight 0 3 kg Installation DIN rail 35 mm 1...

Страница 7: ...connected to the controllers input and output connectors 1 Set all parameters on the controller 2 Make sure that there is no external voltage on the temperature sensor plugs 3 Make sure that the volta...

Страница 8: ...password admin1234 Important Change of password to secure any unauthorized interaction from 3rd parties Note You can Skip login for access to data only in CCR3 reading overview only When the setup and...

Страница 9: ...6 1 open valve output closed to C powered up taking PWM into account 0 valve closed valve output closed to C powered down taking PWM into account Valve is 1 Open if PWM min Valve PWM max 9 Valve valve...

Страница 10: ...for Output which Over temperature or Broken Sensor Higher the value longer the reaction time alarm signal Factory setting 0 min 33 Alarm diff temp Set upper lower deviation temperature counted from R...

Страница 11: ...ed Factory setting Odd 57 Modbus address Unit Address for Mobus RTU RS485 Factory setting 1 58 LAN IP address The IP address that the router assigned to this device when it joined the network This num...

Страница 12: ...s reset to admin00X where x is the number of BT blue LED blinks Reset the setting only Go to firmware menu and click on Return Defaults Reset password only but not change other parameters Go to firmwa...