4 | © Danfoss | 2016.11

EI.96.I3.2U 

AME 20, AME 30

ENGLISH

Safety Note

To avoid injury of persons and 
damages to the device, it is absolutely 
necessary to read and observe these 

instructions carefully.

Necessary assembly, start-up, and maintenance 
work must be performed by qualified and 
authorized personnel only.

Please comply with the instructions of the 
system manufacturer or system operator.

Do not remove the cover before the 
power supply is fully switched off.

Disposal instruction

This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 
disposal. 

Always follow the local disposal regulations.

Mounting

Admissible Installation Positions 

Fix the AME 20, AME 30 on the valve. 

Wiring 

Do not touch anything on the PCB!
Switch off the power line before wire 
the actuator! Lethal voltage!

Wire the actuator according to the wiring 
diagram.

Control signal

Control signal from the controller must be 
connected to terminals Y (input signal) and SN 
(common) on the AME printed board.

Output signal

Output signal from the terminal X can be used 
for indication of the current position. Range 
depends on the DIP switch settings.

Supply voltage

Supply voltage (24 V~ –15 to +10 %, 50/60 Hz) 
must be connected to the terminals SN and SP.

Part Name

Hazardous Substances Table

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hexavalent Chromium (Cr(VI))

Polybrominated biphenyls (PBB)

Polybrominated diphenyl ethers (PBDE)

Housing

X

O

O

O

O

O

Nut

X

O

O

O

O

O

Bushings

X

O

O

O

O

O

O:  Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X:  Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirement in GB/T 26572;

DIP switch settings 

U

I

2 V_--- V

0 V_--- V

Direct

Inverse

---

Sequential

0(2)_5(6) V

5(6)_10 V

Proportional

3 point/RL

LOG. flow

LIN. flow

100 % k

VS

RED. k

VS

Reset

Reset

 

Factory settings: 
ALL switches are on OFF position! 

❹①

 

Note:

 

All combinations of DIP switches are 

allowed. All functions that are selected are 
added consecutively. There is only one logic 
override of functionalities i.e. the switch No.6 
Proportional/3 point, which sets actuator to 
ignore control signal and works as a “simple” 
3-point actuator.

SW1: U/I 

❹②

  Factory settings: 

Voltage control signal (0-10 V).

SW2: 2-10 V/0-10 V 

❹③

  Factory settings: 

2-10 V.

SW3: Direct/Inverse 

❹④

 

Factory settings: 
DIRECT

SW4:---/Sequential

 

❹⑤

Two actuators can be set to work parallel with 
one control signal. If the SEQUENTIAL is set then 
an actuator responds to split control signal (see 
0(2)-5(6) V/5(6)-10 V).

 

Note: 

This combination works in combination 

with switch No.5: 0(2)-5(6) V/5(6)-10 V

SW5: 0(2)-5(6) V/5(6)-10 V

 

❹⑥

 

Note: 

This function is available if switch No.4:  

---/Sequential is set. 

SW6: Proportional/3 point 

❹⑦

 

Actuator needs to perform Self 
stroking prior changing DIP 6 to ON.
Output signal depends on DIP 2, 3&5 
setting.

Actuator can operate in modulating (DIP 6 to 
OFF) or in “simple” 3-point mode, if the 3-point 
function is selected (DIP 6 to ON). 

Connect power supply on terminals SN and SP 
terminals.

Factory set DIP 6 to OFF for operating actuator 
in Modulating mode.

Actuator’s stem will run to its totally extended 
or retracted position by bridging SN signal to 
terminals 1 or 3 and will remain in this positron 
as long as potential is present. 

Set DIP 6 to ON for operating actuator in 3 point 
mode.

Look carefully wiring diagram as wiring is 
different for controllers with triac output (ECL) 
in comparison to controllers with relay output.

Return signal X indicates the correct position.

 

Note:

 If 

3 point

 function is selected actuator 

does not respond to any control signal on 
port Y. It only rises and lowers spindle if power 
is supplied on port 1 or 3.

SW7: 

LOG/LIN - Not in use. 

SW8:

 100% k

VS

/Reduced k

VS

 - Not in use. 

SW9: Reset 

❹⑧

 

After the actuator has been connected to 
power supply, the actuator will start the 
self-adjustment procedure. The indicator LED 
flashes until self adjustment is finished. The 
duration depends on the spindle travel and will 
normally last a few minutes. The stroke length 
of the valve is stored in the memory after self 
adjustment has been completed. To restart 
self adjustment, change the position of RESET 
switch (switch No.9). If the supply voltage is 
switched off or falls below 80 % in more than 
0.1 s, the current valve position will be stored 
in the memory and all data remain saved in the 
memory also after a power supply cut-out.

Function test

The indicator light shows whether the 
positioner is in operation or not. Moreover, the 
indicator shows the control status and faults.
Constant light

-  normal operation

No light 

-  no operation or no power supply

Intermittent light (1 Hz)  

-  self adjusting-mode

Intermittent light (3 Hz): 

-  power supply too low
-  insufficient valve stroke (<20 s)
-  end-position cannot be reached.

Dimensions 

Содержание AME 20

Страница 1: ...8 SVENSKA AME 20 AME 30 www danfoss com Page 9 NEDERLANDS AME 20 AME 30 www danfoss nl Page 10 ROM N AME 20 AME 30 www incalzire danfoss com Pagina 11 SUOMI AME 20 AME 30 www danfoss fi Sivu 12 POLSKI...

Страница 2: ...2 10 V Output Proportional 3 point RL Wiring for modulating mode SN 0 V Neutral SP 24 VAC Power supply 1 24 VAC Input 3 X 0 2 10 VDC Output Proportional 3 point RL Wiring for 3 point floating mode Con...

Страница 3: ...VB 2 DN 15 50 AME 20 AME 30 AVQM PN 25 DN 32 50 H 6 U I 2 V_ V 0 V_ V Direct Inverse Sequential 0 2 _5 6 V 5 6 _10 V Proportional 3 point RL LOG flow LIN flow 100 k VS RED k VS Reset Reset 155 83 min...

Страница 4: ...10 V SW2 2 10 V 0 10 V Factory settings 2 10 V SW3 Direct Inverse Factory settings DIRECT SW4 Sequential Two actuators can be set to work parallel with one control signal If the SEQUENTIAL is set then...

Страница 5: ...ing DIREKTE SW4 Sekvens To aktuatorer kan arbejde parallelt med et reguleringssignal I SEKVENS indstilling reagerer aktuatoren p delt styresignal se 0 2 5 6 V 5 6 10 V Bem rk Denne kombination arbejde...

Страница 6: ...Zwei Antriebe k nnen parallel mit einem Steuersignal arbeiten Bei der Einstellung SEQUENTIAL Antrieb reagiert auf geteilten Steuersignal sehe 0 2 5 6 V 5 6 10V Bemerkung Diese Kombination funktionier...

Страница 7: ...t tre r gl s de telle mani re qu ils fonctionnent parall lement avec un signal de commande Si la fonction S QUENTIEL est r gl e le moteur r pond au signal de commande split voir 0 2 5 6 V 5 6 10 V Rem...

Страница 8: ...ue respondan a la misma se al de control a la vez Al elegir SEQUENTIAL el actuador responder a la se al de control dividida vease 0 2 5 6 V 5 6 10 V Nota Esta combinaci n funciona en combinaci n con e...

Страница 9: ...n till att ignorera styrsignalen och arbeta som en enkel 3 punkts motor SW1 U I Fabriksinst llning Sp nningssignal 0 10 V SW2 2 10 V 0 10 V Fabriksinst llning 2 10 V SW3 Direkt Indirekt Fabriksinst ll...

Страница 10: ...tional 3 point welke de motor instelt als simpele 3 punts servomotor SW 1 U I De servomotor kan reageren op een spannings stuursignaal U of een stroom stuursignaal I Het spanningsbereik is 0 10 V het...

Страница 11: ...2 2 V 10 0 V 10 Setarea de fabric este 2 10 V SW3 Direct Invers Setarea de fabric este DIRECT SW4 Secven ial Dou servomotoare pot fi setate s lucreze n paralel cu un singur semnal de comand Dac este s...

Страница 12: ...i 0 10 V Tehdasasetus 2 10 V SW3 Suora tai k nteinen Tehdasasetus SUORA SW4 vaiheittainen Kaksi k ytt laitetta voidaan m ritt toimimaan rinnakkain samasta ohjaussignaalista Jos vaiheittaisuus otetaan...

Страница 13: ...V SW3 Direct Inverse Ustawienie fabryczne DIRECT SW4 Sequential Dwa si owniki mog by sterowane r wnolegle jednym sygna em steruj cym Je li wybrana jest opcja SEQUENTIAL si ownik reaguje na dzielony s...

Страница 14: ...5 6 V 5 6 V_10 V 3 RL 100 Kvs Red Kvs OFF DIP 6 SW1 U I 0 10 B SW2 2 10 B 0 10 B 2 10 B SW3 SW4 0 2 5 6 5 6 10 5 0 2 5 6 5 6 10 SW5 0 2 5 6 5 6 10 4 SW6 DIP 6 DIP 2 35 DIP6 OutputsignaldependsonDIP2 3...

Страница 15: ...r VI PBB PBDE X O O O O O X O O O O O X O O O O O O GB T 26572 X GB T 26572 DIP U I 2 V_ V 0 V_ V 0 2 V_5 6 V 5 6 V_10 V RL LOG flow LIN flow 100 kVS RED kVS Reset Reset _ OFF DIP 6 SW1 U I SW2 2 10 V...

Страница 16: ...erves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed...

Отзывы: