11. DOMESTIC HOT WATER

General information

PLEASE NOTE! Some models may have a slightly different appearance, 

but the control function is in principle the same as described below.

Commissioning

Commission the substation in accordance with the instructions in 

this manual.

Regulation of domestic hot water temperature

The domestic hot water is prepared in the heat exchanger based on 

the flow principle and the temperature is controlled by a combined 

hydraulic and thermostatic self-acting controller 

PTC2+P 

with in-

tegrated differential pressure controller, which blocks the flow of 

primary and secondary side flow through the heat exchanger im-

mediately after completion of the tapping process. 

PTC2 controller for DHW (Fig. 1). 

Adjust the hot water temperature by moving the adjuster lever to-

wards “+” (hotter) or “-” (colder). Start by turning the lever clockwise 

– until it stops/until you cannot turn it any further. Then turn the lever 

counter-clockwise until the temperature of the tap water is approx. 

48°C during normal tapping flow (7–8 litres per min.). The temperature

must never exceed 55°C to prevent limescale deposits building up

in the water heater.

Bypass thermostat (default)

As a standard the substation is equipped with a bypass thermostat, 

Danfoss FJVR, so that when water is tapped, the water heater 

immediately starts to produce hot water. We recommend setting 

of the thermostat in pos.3. If you have to wait a long time (i.e. more 

than 20 sec.) for hot water, it may be necessary to set the thermostat 

at a higher value.

If you want to avoid waiting time altogether, you will need to set up 

domestic hot water recirculation to the tapping points.

Circulations thermostat / conversion to recirculation

If the household piping system features domestic hot water recir-

culation, the substation must be connected to the recirculation sys-

tem.

Scale setting (indicative)

Pos. 2 = 30°C

 

3 = 40°C

 

4 = 45°C

Conversion to recirculation requires only an additional circulation 

set. (This is not part of the delivery and must be purchased as extra 

equipment, - see photo on page 10). 

Connect the recirculation pipe from the fixed household piping sys-

tem to the hexagon nipple at the bottom of the substation (please see 

page 10 for instructions about how to make recirculation connection).

If a time-controlled pump is used, we recommend setting the circu-

lation water temperature to approx. 35 °C.

Abb. 

Adjuster lever

Fig. 1

Fig. 2

Содержание Akva Lux II TDv

Страница 1: ...Dv Fully insulated district heating substation for district heating and in stantaneous DHW Fullyinsulateddistrictheatingsubstationforlow temperaturedistrictheatingandinstantaneousdomestichotwater Akva...

Страница 2: ...ple 8 7 0 General 9 8 0 Recirculation 10 9 0 Safety set 13 10 0 Adjustment and commissioning 14 11 0 Domestic hot water 16 12 0 Maintenance 17 13 0 Troubleshooting 19 14 0 EU Declaration of conformity...

Страница 3: ...red in a dry heated i e frost free room Relative humidity max 80 and storage temperature 5 70 C Theunitsmustnotbestackedhigherthanthelimitatthefactory max 8layers Unitssuppliedincardboardpackagingmust...

Страница 4: ...rictheatingsta tionsandplumbinginstallations Equipotentialbondingshouldbeinac cordancewiththeprovisions60364 4 41 2007andIEC60364 5 54 2011 Binding point is marked with a grounding symbol on the botto...

Страница 5: ...eaththeunit foruseonDHWandheatingsystemswithconcealedpipeinstallations Heat exchanger for DHW heating The substation is based on a brazed highly efficient plate heat exchanger which is controlled by a...

Страница 6: ...ax 8mm screws expansion bolts or similar 2 Close all shut off valves before the water heater is connected to the household piping 3 Tighten all pipe connections as they may have loosened during trans...

Страница 7: ...afety set for mounting underneath substation 145H3001 Actuator TWA Q for zone valve Supplement for stainless steel HEX XB 06H 1 26StS 26 pl Supplement for stainless steel HEX XB 06H 1 40StS 40 pl 5 MA...

Страница 8: ...Akva Lux II TDv DH Return DHW DCW DH Supply 2 Plate heat exchanger DHW 4 Differential pressure controller AVPL 5 Strainer 38 DHW controller PTC2 P 40 Danfoss FJVR for bypass circ 52 Zone valve RA C D...

Страница 9: ...a Lux II TDv substations can be removed without using tools Take hold of the air duct in the top and bottom of the front insulation section and pull carefully forward until the front insulation sectio...

Страница 10: ...ted on the circulation pipe of the substation Seepages10to12forinformationaboutpreparation ofsubstationforandconnectiontotheDHWrecirculationsystem Remember always to mount circulation pump and non ret...

Страница 11: ...controller Fig 3 Mount circulation hose end B1 in controller Fig 4 Unscrew the 3 screws on locking rail Fig 5 Demount locking rail Fig 6 Demount support rail as shown Fig 7 GB Place bracket C on suppo...

Страница 12: ...port rail Fig 14 Fit new capillary tube G on nipple B by means of union nut and cutting ring H Tighten with single end wrench Fig 15 Fit the other end of the capillary tube G on T piece by means of un...

Страница 13: ...ems with recirculation For mounting underneath unit Please note that the safety kit shown can be used on different unit types and that there may therefore be components pipe pieces that should not be...

Страница 14: ...just ment is made according to the instructions in this manual Commissioning Commission the substation in accordance with the instruction manual Heating circuit Differential Pressure Controller The di...

Страница 15: ...s controlled by the room thermostat and radiator thermostats Please note that the room thermostat keeps the temperature at a constant level in the whole apartment according to the set room parameters...

Страница 16: ...Thetemperature must never exceed 55 C to prevent limescale deposits building up in the water heater Bypass thermostat default As a standard the substation is equipped with a bypass thermostat Danfoss...

Страница 17: ...cause aerated water is used on the secondary side If it becomes necessary to clean the exchanger with acid this canbedoneasshownonthedrawingtotheright Brazedplateheat exchangers can withstand rinsing...

Страница 18: ...e component in question Clean all dirt filters strainers in the substation Replace any filters that are not intact Check that any electrical cables are in ser viceable condition and that it is possibl...

Страница 19: ...ctions Poor cooling Insufficient heating surface radiators too small compared to the total heating requirement of the building Poor utilisation of the existing heating sursurface Increase total heatin...

Страница 20: ...in the pump housing No hot water Dirt strainer in the district heating sup ply line clogged Defective DHW controller Defective sensor PTC2 Clean the dirt strainer Check controller settings You may con...

Страница 21: ...eat exchanger Short circuited heat exchanger Clean heat exchanger with acid solution or replace heat exchanger Replace heat exchanger Discoloured water for a longer period Short circuited heat exchang...

Страница 22: ...22 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv 14 EU DECLARATION OF CONFORMITY...

Страница 23: ...ions and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for leaks before del...

Страница 24: ...o 0 5 Good corrosion resistance o Corrosion could happen when more parameters are evaluated with o o Risk of corrosion Use is not recommended Hardness ration limits defined per experience and interna...

Страница 25: ...25 25 Danfoss District Energy 145X2085 AQ428255318526en 010101 DKDHR Instructions Akva Lux II TDv...

Страница 26: ...26 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv...

Страница 27: ...27 27 Danfoss District Energy 145X2085 AQ428255318526en 010101 DKDHR Instructions Akva Lux II TDv...

Страница 28: ...28 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv...

Отзывы: