13. TROUBLE SHOOTING - DOMESTIC HOT WATER

Problem

Possible cause

Solution

DHW*, no hot water

Non-return valve in the circulation pipe 

defective (leads to mixing - the circula-

tion water pipes become cold during 

tapping).

Replace the non-return valve.

Temperature too low / variations in 

temperature

Non-return valve in thermostatic mixer 

in the bathroom defective - results in hot 

and cold water mixing. Please note that 

fluctuating temperatures may occur at 

other tapping points in the system!

NB, Check all mixers in the house for 

faults/defects!

Replace the mixer or perhaps only the 

non-return valve.

Lack of hot water pressure

Clogged strainer in the cold water meter 

or possibly in the cold water supply in 

the unit.
Calified heat exchanger.

Clean the strainer (cold water meter, 

in consultation with the water supply 

company).
Replace the heat exchanger.

Long wait for hot water

Circulation pump out of order.

Check whether the pump is running - 

and whether there is a power supply to 

the pump. Make sure that there is no air 

in the pump housing. 

No hot water

Dirt strainer in the district heating sup-

ply line clogged.

Defective DHW controller.

Defective sensor. (PTC2)

Clean the dirt strainer.

Check controller settings. You may con-

tact Danfoss Redan A/S for further infor-

mation.

Replace sensor.

Hot water temeprature too low

As above.

Non-return valve in the circulation pipe 

defective (leads to mixing - the circulation 

water pipes become cold during ).

As above.

Replace non-return valve.

Hot water temperature too high

Defective domestic hot water controller.

Check the function of the DHW control-

ler and replace if defective.

Temperature falls during tapping (lack 

of capacity)

Air in the capillary tube for the differen-

tial pressure controller.

Calified plate heat exchanger.

Vent the capillary pipe.

Replace the plate heat exchanger.

Fundamental

In the event of disruptions to operation, you should fundamentally - before commencing the actual troubleshooting - check 

whether:
•  the system is correctly connected

•  the district heating supply temperature is at its normal level

•   the differential pressure is at its normal level. Ask your district 

      heating supplier if necessary

•  there is a power supply to the system - pump and automatics 

•  the dirt strainer in the district heating supply pipe is clean

•  there is air in the system (if the system is vented)

Содержание Akva Lux II TDv

Страница 1: ...Dv Fully insulated district heating substation for district heating and in stantaneous DHW Fullyinsulateddistrictheatingsubstationforlow temperaturedistrictheatingandinstantaneousdomestichotwater Akva...

Страница 2: ...ple 8 7 0 General 9 8 0 Recirculation 10 9 0 Safety set 13 10 0 Adjustment and commissioning 14 11 0 Domestic hot water 16 12 0 Maintenance 17 13 0 Troubleshooting 19 14 0 EU Declaration of conformity...

Страница 3: ...red in a dry heated i e frost free room Relative humidity max 80 and storage temperature 5 70 C Theunitsmustnotbestackedhigherthanthelimitatthefactory max 8layers Unitssuppliedincardboardpackagingmust...

Страница 4: ...rictheatingsta tionsandplumbinginstallations Equipotentialbondingshouldbeinac cordancewiththeprovisions60364 4 41 2007andIEC60364 5 54 2011 Binding point is marked with a grounding symbol on the botto...

Страница 5: ...eaththeunit foruseonDHWandheatingsystemswithconcealedpipeinstallations Heat exchanger for DHW heating The substation is based on a brazed highly efficient plate heat exchanger which is controlled by a...

Страница 6: ...ax 8mm screws expansion bolts or similar 2 Close all shut off valves before the water heater is connected to the household piping 3 Tighten all pipe connections as they may have loosened during trans...

Страница 7: ...afety set for mounting underneath substation 145H3001 Actuator TWA Q for zone valve Supplement for stainless steel HEX XB 06H 1 26StS 26 pl Supplement for stainless steel HEX XB 06H 1 40StS 40 pl 5 MA...

Страница 8: ...Akva Lux II TDv DH Return DHW DCW DH Supply 2 Plate heat exchanger DHW 4 Differential pressure controller AVPL 5 Strainer 38 DHW controller PTC2 P 40 Danfoss FJVR for bypass circ 52 Zone valve RA C D...

Страница 9: ...a Lux II TDv substations can be removed without using tools Take hold of the air duct in the top and bottom of the front insulation section and pull carefully forward until the front insulation sectio...

Страница 10: ...ted on the circulation pipe of the substation Seepages10to12forinformationaboutpreparation ofsubstationforandconnectiontotheDHWrecirculationsystem Remember always to mount circulation pump and non ret...

Страница 11: ...controller Fig 3 Mount circulation hose end B1 in controller Fig 4 Unscrew the 3 screws on locking rail Fig 5 Demount locking rail Fig 6 Demount support rail as shown Fig 7 GB Place bracket C on suppo...

Страница 12: ...port rail Fig 14 Fit new capillary tube G on nipple B by means of union nut and cutting ring H Tighten with single end wrench Fig 15 Fit the other end of the capillary tube G on T piece by means of un...

Страница 13: ...ems with recirculation For mounting underneath unit Please note that the safety kit shown can be used on different unit types and that there may therefore be components pipe pieces that should not be...

Страница 14: ...just ment is made according to the instructions in this manual Commissioning Commission the substation in accordance with the instruction manual Heating circuit Differential Pressure Controller The di...

Страница 15: ...s controlled by the room thermostat and radiator thermostats Please note that the room thermostat keeps the temperature at a constant level in the whole apartment according to the set room parameters...

Страница 16: ...Thetemperature must never exceed 55 C to prevent limescale deposits building up in the water heater Bypass thermostat default As a standard the substation is equipped with a bypass thermostat Danfoss...

Страница 17: ...cause aerated water is used on the secondary side If it becomes necessary to clean the exchanger with acid this canbedoneasshownonthedrawingtotheright Brazedplateheat exchangers can withstand rinsing...

Страница 18: ...e component in question Clean all dirt filters strainers in the substation Replace any filters that are not intact Check that any electrical cables are in ser viceable condition and that it is possibl...

Страница 19: ...ctions Poor cooling Insufficient heating surface radiators too small compared to the total heating requirement of the building Poor utilisation of the existing heating sursurface Increase total heatin...

Страница 20: ...in the pump housing No hot water Dirt strainer in the district heating sup ply line clogged Defective DHW controller Defective sensor PTC2 Clean the dirt strainer Check controller settings You may con...

Страница 21: ...eat exchanger Short circuited heat exchanger Clean heat exchanger with acid solution or replace heat exchanger Replace heat exchanger Discoloured water for a longer period Short circuited heat exchang...

Страница 22: ...22 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv 14 EU DECLARATION OF CONFORMITY...

Страница 23: ...ions and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for leaks before del...

Страница 24: ...o 0 5 Good corrosion resistance o Corrosion could happen when more parameters are evaluated with o o Risk of corrosion Use is not recommended Hardness ration limits defined per experience and interna...

Страница 25: ...25 25 Danfoss District Energy 145X2085 AQ428255318526en 010101 DKDHR Instructions Akva Lux II TDv...

Страница 26: ...26 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv...

Страница 27: ...27 27 Danfoss District Energy 145X2085 AQ428255318526en 010101 DKDHR Instructions Akva Lux II TDv...

Страница 28: ...28 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv...

Отзывы: