© Danfoss | DCS (MWA) | 2017.07
DKRCI.PI.SC0.F3.ML | 520H8392 | 9
Default screen
• Press
• Press
• Press
Enter password:
• Press 4 times.
• Press
• Press 2 times.
• Press to check/change GAS EPS.R.
(Select the correct value from the tables
below and on page 8)
Press to change cursor-
position.
Press to decrease the value or to
increase the value.
• Press to confirm.
• Press 3 times.
• Press or to select between
STORE NO or STORE YES.
Select STORE YES by pressing
Default screen appears:
Entering the dielectric constant of
refrigerant gas completed
How to enter dielectric constant of refrigerant gas (all values below are only examples)
Optional Procedure
If the temperature condition in the stand pipe is known, a constant (dielectric constant of the refrigerant gas) can be entered
(parameter 2.5.3 GAS EPS.R), in order to obtain lower Top and Bottom Dead Zone values (see fig. 5).
AKS 4100
QUICK SETUP ?
YES NO
Saturated vapour dielectric constant (default value: 1.066)
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -42
-76 – -43
1.00
-41 – -18
42 – 0
1.01
-17 – -5
1 – 23
1.02
-4 – 4
24 – 39
1.03
5 – 12
40 – 54
1.04
13 – 18
55 – 64
1.05
19 – 24
65 – 75
1.06
25 – 28
76 – 82
1.07
29 – 33
83 – 91
1.08
34 – 37
92 – 99
1.09
38 – 40
100 – 104
1.10
41 – 44
105 – 111
1.11
45 – 47
112 – 117
1.12
48 – 50
118 – 122
1.13
R717 (NH
3
)
Temperature range:
-60 – 50 °C / -76 – 122 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-56.0 – -42.0
-69 – -43
1.01
-41.0 – -28.0
-42 – -18
1.02
-27.0 – -17.0
-17 – 2
1.03
-16.0 – -9.0
3 – 16
1.04
-8.0 – -3.0
17 – 27
1.05
-2.0 – 2
28 – 36
1.06
3 – 7
37 – 45
1.07
8 – 11
46 – 52
1.08
12 – 14
53 – 58
1.09
15
59
1.10
R744 (CO
2
)
Temperature range:
-56 – 15 °C / -69 – 59 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -50
-76 – -58
1.00
-49 – -25
57 – -13
1.01
-24 – -10
-12 – 14
1.02
-9 – 0
15 – 32
1.03
1 – 8
33 – 46
1.04
9 – 15
47 – 59
1.05
16 – 21
60 – 70
1.06
22 – 26
71 – 79
1.07
27 – 31
80 – 88
1.08
32 – 35
89 – 95
1.09
36 – 39
96 – 102
1.10
40 – 42
103 – 108
1.11
43 – 45
109 – 113
1.12
46 – 48
114 – 118
1.13
R22
Temperature range:
-60 – 48 °C / -76 – 118 °F
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
-60 – -42
-76 – -43
1.00
-41 – -18
-42 – -0
1.01
-17 – -4
1 – 25
1.02
-3 – 5
26 – 41
1.03
6 – 13
42 – 56
1.04
14 – 20
57 – 68
1.05
21 – 25
69 – 77
1.06
26 – 30
78 – 86
1.07
31 – 34
87 – 94
1.08
35 – 38
95 – 100
1.09
39 – 42
101 – 108
1.10
43 – 45
109 – 113
1.11
46 – 48
114 – 119
1.12
49 – 50
120 – 122
1.13
R134a
Temperature range:
-60 – 50 °C / -76 – 122 °F
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK SETUP
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
___________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.5.0
APPLICATION
AKS 4100
2.5.1
TRACING VEL.
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
GAS EPS. R
1.066