Navigate through the various control lines,
enter custom description & valid address
(Board & Point) that reflect the location on
the AK I/O network
ALARMS
Configuration->Control->LIGHT->Alarms
After the relevant Lighting control questions and appropriate AK
I/O addresses have been applied, check the alarms tab. Depend-
ing on the Lighting control configuration alarm points will be
seen under the alarm tab.
ADDRESSES
Configuration->Control->LIGHT->Addresses
After the relevant Lighting control questions have been config-
ured, appropriate AK I/O addresses need to be applied. The
address inputs correspond to the Board & Point address of the AK
I/O modules. Depending on the control definition made in the
previous (Configuration->Control->Light) screen various inputs
will require board & point addresses. Navigate through the
Relays, Sensors, On/Off Inputs & variable tabs to define the
relevant outputs (Skip the controllers tab as all control is done via
AK I/O).
Tip!
Standard schedule (eg. on / off time 8 am to 10pm)
Relative means, relative to the open/closed hours. I.E. Open hours
are 8 am until 10 pm and a certain lighting zone needs to come on
15 minutes prior to start of open hours until 30 minutes after
closing, the schedule would look like the following;
-0015 on --> +0030 off (so, being relative, the lights are on at 7:45
am and off at 10:30 pm