After completing the required settings in the ‘time’ tab, navigate
to the ‘system’ tab. Under the system tab add the store name and
region / preference setting and information.
The Auth (Authorization) Levels tab allows the definition of up to
7 authorization types. Custom authorization types can be
configured with certain system privileges / access. In the
example below, 4 auth levels have been defined (factory setting
is 3). Level 1 (Supervisor) cannot have the settings changed. To
change the level of access of other auth levels, navigate to the
desired line and select from the Authorization pop up dialog box.
As factory standard, 3 levels are predefined (Supervisor, Service,
Daily User), the service and daily user levels can be changed as
required.
To add/delete auth levels select the ‘Number of
authorization types’ line (max 7 levels)
The Supervisor name can be changed but the level
of access / privileges are factory set.
Adding new auth levels allows new users to have
specific access to key system areas. Once new auth
types have been created, enter custom name and define
level of access by selecting the Settings line (Authoriza-
tion pop up box will appear)
Use this screen to configure
‘Store name/details, unit
name, preferences, system
language’. Double click the
appropriate line to make
changes
‘Color for old controller data’ is
an option to reflect data that
has yet been updated via a
network poll. Data with a *
indicates either an offline
condition or that the AK-SM is
waiting for a fresh update
from the device
Legacy I/O type is used to set
legacy supported devices
The Users screen allows the
definition of up to 20 users
The Auth (Authorization) screen allows
the definition of up to 7 authorization
types.
Reflects what license is
configured for your AK-SM.
Different license allow
additional functionality
The system report screen allows the user to define
what content should be included.
Alarms, Schedules, scanned devices, Audit trail and
controller database are available options.
To generate a system report go the main web menu
and select File/Download Report