Set the parameter d1=2 for the management of heater defrost by time with temperature control. 

During the defrost the output is activated when the evaporator’s temperatures are lower than d2. 

Defrost stops after d3 minutes. It allows energy saving and a better defrost process.

Set parameter d1=1 to defrost in cycle inversion mode.

The compressor relay and defrost relay are activated throughout the defrost phase.

To ensure proper control of the system the installer must use the defrost output: this must allow 

opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve.

For capillary systems (without thermostat valve) it is only necessary to control the cycle inversion 

solenoid valve via the defrost relay control.

Pump down function is activated when parameter AU1/AU2 = 4 / -4.

Connect pump down pressostat on the digital input configured as pump down (In1 or In2 = 4 / -4). 

The compressor is directly controlled by pressostat. Connect evaporator solenoid valve on the AUX1 

(or AUX2) relay. The solenoid is controlled directly by thermostat.

When parameter PA is setting with value different to 0 the protection function is activated.

See parameter P1 for the different protection.

When PA is setting the protection start after two minutes of inactivity. On display appear 000. With up/

down modify the number, with set key confirm it.

Use universal number 100 if you don’t remember the password.

For 

RS-485

 connections with 

Modbus-RTU

 protocol follow the scheme below.

AK-RC 111

Содержание AK-RC 111

Страница 1: ...User Guide Optyma control AK RC 111 single phase...

Страница 2: ...ing and displaying the set points 8 4 7 Level 1 programming user level 8 4 8 List of Level 1 variables user level 8 4 9 Level 2 programming installer level 9 4 10 List of Level 2 variables installer l...

Страница 3: ...iliary relays with parameter configured Integrated RS 485 Modbus connection for Danfoss System Manager or standard Modbus RTU network Emergency operation in the event of a faulty probe environment Sma...

Страница 4: ...n the electronics For the purposes of assembly and use the electronic AK RC 111 control unit comes with 3 seals to be fitted between the fixing screws and the box back panel 1 user s manual Fig 1 Rais...

Страница 5: ...e panel and carry out thorough reading programming of all the parameters Note Make all the electrical connections as illustrated in the diagram for the corresponding model see relative table in append...

Страница 6: ...nstalled relay Card output characterstics Note Compressor Relay 30A AC1 10 A 250 V AC3 2HP 100000 cicli The sum of contemporary absorptions of these outputs has not to exceed 16 A Defrost Relay 30A AC...

Страница 7: ...Cold room temperature parameters 7 Up Mute buzzer alarm 2 Stand by flashes on stand by outputs are deactivated 8 Room light flashes if door switch activated 9 Cold indicates activation of compressor 1...

Страница 8: ...T key together with the or key When configuration values have been set you can exit the menu by pressing the or keys simultaneously for a few seconds until the cold room temperature reappears 5 The ne...

Страница 9: ...d working for the F6 time If activation time coincides with the defrosting time end of defrosting is awaited 0 240 min 0 function not activated 0 min F7 Evaporator fans duration for air recirculation...

Страница 10: ...he temperature value read by the evaporator sensor is higher than this value 45 99 C 99 C Fd Fst differential 1 10 C 2 C LSE Minimum value attributable to setpoint 45 HSE 1 C 45 C HSE Maximum value at...

Страница 11: ...econd level programming not permitted 3 PA Password see P1 for the type of protection 0 999 0 not active 0 reL Release software indicates software version 2 read only 4 11 Switching on the AK RC 111 e...

Страница 12: ...must allow opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve For capillary systems without thermostat valve it is only necessary to control the cycle inversion so...

Страница 13: ...room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm one where applicable are deactivated...

Страница 14: ...front opening hinge 5 Box closure screws 6 Board fixing screws 7 Magneto thermal cut out power breaker 8 CPU board 9 Polycarbonate screw cover 10 Terminal for earth connections N F d d 1 2 3 4 5 6 7...

Страница 15: ...User Guide Optyma control AK RC 111 single phase Danfoss DCS vt 2020 03 BC309238530328en 000101 15 8 0 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3220...

Страница 16: ...oss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady...

Отзывы: